12
To manage the alarm associated with snow, the temperature and the rain sensors must be combined.
SNOW condition
1.1
4.3
Factory setting
DEACTIVATED
SNOW
Alarm priority
MEDIUM
ALARM ACTIVATED when
What happens with ALARM ACTIVATED
ALARM NOT ACTIVE when
The measured temperature is below 2 °C
and rain has been detected (see par.
4.4
)
The control unit tilts the slats to
66%
of full opening. The control
unit only executes
hold-to-run commands
.
The measured temperature is above 3 °C or
rain is no longer detected.
L4
P2
ACTIVATION
The motor must be
stopped.
*
x7
DEACTIVATION
The motor must be
stopped.
*
x7
HOLD
**
(5 s)
continuous
sound
**
Activation/Deactivation
of SNOW condition with P2.
* The buzzer will make a beep each time the button is pressed. ** The motors make short movements
ALARM ACTIVATED when
What happens with ALARM ACTIVATED
ALARM NOT ACTIVE when
The sensitive surface of the sensor detects
drops of water.
The control unit completely
CLOSES
the pergola slats. The
control unit executes
no command
.
The sensor doesn’t detect any drop.
System operation AFTER rain alarm (draining of water):
once the rain alarm has ended, for the following
6 hours
the control unit, upon receiving an
automatic movement command from the transmitter, will tilt the pergola slats to
33%
to allow water to drain off. For
4 minutes
the control unit can only execute
hold-to-run commands, thereby exiting from the alarm status.
RAIN sensor
1.1
4.4
Factory setting
ACTIVATED
Alarm priority
LOW
RAIN
L4