TELCOSAT RPT 900
Document use is restricted to that described on cover
15
REPEATER SET UP PAGE
4.4
The Repeater Set-up Page is where all adjustments/settings are performed. Enter the required setting in
the box and then click the “Save Settings” box. You can verify the setting by reviewing the “Status Page”
4.5
ALARM THRESHOLDS
Alarm thresholds will send an email alerting that the number in the threshold boxes have be reached.
For example, the Temperature high alarm box is set to 70c°. If the temperature of the repeater reaches
70c° an email alert will be sent from the repeater.
Setting the Alarm Thresholds
Power up the repeater, allow the unit to warm up to operating temperature, log in and go to the
Repeater “Status Screen”. Look for the Repeater Status Screen, then look for Working Status Box on
the
same page.
DC current of the Forward Link and the DC current of the Reverse Link.
4.6
High Current Alarm Settings
Using the data from the manual for this example only, REPEATER STATUS PAGE,
Displayed is DC current Forward Link 91mA
Displayed is DC current Reverse Link 85mA.
This is the normal operating current from your repeater and should be used as a guide line for Alarm
Threshold.