Setting
Display
SET HEAT FLOOR
Set the floor heating temperature for the event.
Floor
Access Level: Installer, User
Range: 40 to 95°F (4.5 to 35.0°C)
Conditions: Room Sensor set to OFF and Sensor
1 or Sensor 2 set to Floor and Schedules are in
use or Scenes are set to All or Guest.
Default: 65°F (18.5°C)
WARM WEATHER SHUT DOWN
Set the outdoor air temperature at which heating is
suspended during the event.
Access Level: Installer
Range: CTRL (control), 40 to
100°F (4.5 to 38.0°C), OFF
Conditions: An outdoor sensor must be available.
Default: CTRL (with tN System
Control or 70°F (21°C) (Standalone)
WARM WEATHER SHUT DOWN
Set the outdoor air temperature at which heating is
suspended during the event.
Access Level: Installer
Range: CTRL (control), 40 to
100°F (4.5 to 38.0°C), OFF
Conditions: An outdoor sensor must be available and
Schedules are in use or Scenes is set to All or Guest.
Default: CTRL (with tN System
Control or 60°F (15.5°C) (Standalone)
SET COOL ROOM
Set the room cooling temperature for the event.
Access Level: Installer, User
Range: 50 to 100°F
(10.0 to 38.0°C)
Conditions: Y RELAY is set to HP or AC.
Default: 78°F (25.5°C)
SET COOL ROOM
Set the room cooling temperature for the event.
Access Level: Installer, User
Range: 50 to 100°F
(10.0 to 38.0°C)
Conditions: Y RELAY is set to HP or AC and
Schedules are in use or Scenes is set to All or Guest.
Default: 85°F (29.5°C)
SET COOL ROOM AWAY
Set the room cooling temperature during the Away
scene.
Access Level: Installer
Range: 50 to 100°F
(10.0 to 38.0°C)
Conditions: Y RELAY is set to HP or AC and
scenes is set to Away, All or Guest.
Default: 85°F (29.5°C)
Set Temp Menu (2 of 4)