Set Temp Menu (1 of 4)
Setting
Display
SET HEAT ROOM
Set the room heating temperature for the event.
Room
Access Level: Installer, User
Range: 40 to 95°F (4.5 to 35.0°C)
Conditions: Always available.
Default: 70°F (21.0°C)
SET HEAT ROOM
Set the room heating temperature for the event.
Room
Access Level: Installer, User
Range: 40 to 95°F (4.5 to 35.0°C)
Conditions: Schedules are in use or Scenes are
set to All or Guest.
Default: 65°F (18.5°C)
SET HEAT ROOM AWAY
Set the room heating temperature for the Away
scene.
Room
Access Level: Installer, User
Range: 40 to 95°F (4.5 to 35.0°C)
Conditions: Scenes is set to Away, All or Guest.
Default: 62°F (16.5°C)
HEAT MINIMUM ROOM LIMIT
Set the minimum room heating limit.
Access Level: Installer
Range: 40 to 95°F (4.5 to 35.0°C)
Conditions: Always available.
Default: 40°F (4.5°C)
HEAT MAXIMUM ROOM LIMIT
Set the maximum room heating limit for the
event.
Access Level: Installer
Range: 40 to 95°F (4.5 to 35.0°C)
Conditions: Always available.
Default: 85°F (29.5°C)
HEAT MAXIMUM ROOM LIMIT
Set the maximum room heating limit for the
event.
Access Level: Installer
Range: 40 to 95°F (4.5 to 35.0°C)
Conditions: Schedules are in use or Scenes are
set to All or Guest.
Default: 85°F (29.5°C)
SET HEAT FLOOR
Set the floor heating temperature for the event.
Floor
Access Level: Installer, User
Range: 40 to 95°F (4.5 to 35.0°C)
Conditions: Room Sensor set to OFF and Sensor
1 or Sensor 2 set to Floor.
Default: 72°F (22.0°C)