Electrical (Continued)
Install, ground, wire, and maintain your
pump in compliance with the National
Electrical Code (NEC) in the U.S., or the
Canadian Electrical Code (CEC), as
applicable, and with all local codes and
ordinances that apply. Consult your
local building inspector for code
information.
CONNECTION PROCEDURE
1. Connect the ground wire first as
shown in Figure 16, Page 11. The
ground wire must be a solid copper
wire at least as large as the power
supply wires.
2. There must be a solid metal
connection between the pressure
switch and the motor for motor
grounding protection. If the pressure
switch is not connected to the motor,
connect the green ground screw in
the switch to the green ground screw
under the motor end cover. Use a
solid copper wire at least as large as
the power supply wires.
3. Connect the ground wire to a
grounded lead in a service panel, to a
metal underground water pipe, to a
metal well casing at least ten feet
(3M) long, or to a ground electrode
provided by the power company or
the hydro authority.
4. Connect the power supply wires to
the pressure switch as shown in
Figure 16.
You have now completed the wiring
for your pump.
Please go to Page 13 for startup
preparations.
12
Teel Operating Instructions and Parts Manual
4RJ47, 4RJ48, 4RJ49, 4RJ50, 4P035A and 4P036A
Teel Heavy Duty Cast Iron
Convertible Jet Pumps
®
E
N
G
L
I
S
H
AWG WIRE SIZE
1/3
115/230
9.4/4.7
15/15
14/14
10/14
10/14
6/14
6/12
1/2
115/230
12.2/6.1
15/15
12/14
10/14
8/14
6/12
6/12
3/4
115/230
14.8/7.4
20/15
12/14
8/14
6/14
6/12
4/10
1
115/230
14.8/7.4
20/15
12/14
8/14
6/14
6/12
4/10
1
1
⁄
2
115/230
19.2/9.6
30/15
10/14
8/14
6/12
4/10
4/10
WIRING CHART – RECOMMENDED WIRE AND FUSE SIZES
Max. Load
Branch Fuse*
Distance in Feet from Motor to Supply
Motor HP
Volts
Amp
Rating Amp
0 - 100
101 - 200
201 - 300
301 - 400
401 - 500
(*) Fusetrons are recommended instead of fuses on all motor circuits.