24
Chapter 3
D
.
“AN”
W
iring on
T
ypical System with
Thermal Pr
otector
Figure 3-14.
“AN” wiring on typical system with thermal protector.
2 Speed Motor
Connections
T
1
T
2
T
3
L
1
L
2
L
3
Contactor
To Line
# 14 Min.
See Table 3-5
Compressor
Power
To
Control
Circuit
C
1
L
1
L
2
L
3
R
1
R
2
R
3
C
2
Table 3-5: "AN" Wiring on Typical System
with Thermal Protector
Model
AN5590G/H
AN5610G/H
AN5612G/H
AN5614G/H
AN5590G/H
AN5610G/H
AN5612G/H
AN5614G/H
230/200-60-3
230/200-60-3
230/200-60-3
230/200-60-3
460-60-3
460-60-3
460-60-3
460-60-3
#8 TW
#8 TW
#8 TW
#6 TW
#12 TW
#12 TW
#10 TW
#10 TW
92,500
100,000
122,000
140,000
92,500
100,000
122,000
140,000
27
29
36
42
14
14.4
18
20.8
172
183
229
269
86
93.3
116
135
RLA LRA
Capacity
BTU/HR
Min.
Cond.
Size
Voltage
40 A
40 A
50 A
60 A
25 A
25 A
25 A
30 A
Min.
Cont.*
Size
Not Used On
Internal Line Break
Models (G & H Suffix)
Use Copper Conductors Only
24 Volt
Compressor
Sensors
S
1
S
*Contactor ampere rating is at compressor rated voltage.
Line Voltage
C'Case Heaters