TXV 138 08.02
The following table gives allowed values of the CONT control word with
the corresponding selections:
CONT
Input type
Scanner/range type
Format of input data
1)
$8020
Resistance
Pt100, W100 = 1.385
0 to 65535
$8120
temperature
-200 to +850 °C
-2000 to +8500 [0.1°C]
$8022
scanners
Pt100, W100 = 1.391
0 to 65535
$8122
-200 to +850 °C
-2000 to +8500 [0.1°C]
$8027
Ni1000, W100 =
1.617
0 to 65535
$8127
-60 to +200 °C
-600 to +2000 [0.1°C]
$8029
Ni1000, W100 =
1.500
0 to 65535
$8129
-60 to +200 °C
-600 to +2000 [0.1°C]
$8030
Resistance
0 to 630
0 to 65535
$8130
scanners
0 to 6300 [0.1
$8230
0 to 10000
$8032
0 to 2520
0 to 65535
$8132
0 to 25200 [0.1
$8232
0 to 10000
$8040
Current
0 to 20 mA
0 to 65535
$8140
0 to 20000 [
A]
$8240
0 to 10000
$8042
4 to 20 mA
0 to 65535
$8142
40000 to 20000 [
A]
$8242
0 to 10000
$8080
Voltage
0 to 10 V
0 to 65535
$8180
0 to 10000 [1 mV
$8280
0 to 10000
$8082
0 to 2 V
0 to 65535
$8182
0 to 20000 [0.1 mV
$8282
0 to 10000
1)
For details see item 5.1.5
The following example gives declaration of the TC634 module connected
according to Figs. 9.21 a 9.22.
#table word Ini634 = $8140, ;AI0 - 0 to 20mA/µA
$8142, ;AI1 - 4 to 20mA/µA
$8180, ;AI2 - 0 to 10V/mV
$8182, ;AI3 - 0 to 2V/0,1mV
$8120, ;AI4 - Pt100, W100 = 1.385/0,1°C
$8122, ;AI5 - Pt100, W100 = 1.391/0,1°C
$8127, ;AI6 - Ni1000, W100 = 1.617/0,1°C
$8129 ;AI7 - Ni1000, W100 = 1.500/0,1°C
#unit 0, 1, Analog_600_, 16, 0, R0, X_On, Ini634
; TC634 in position 1. EM
; data from R0
Valid values of the
TC634 control word
Example of TC634
declaration