Technical equipment of TC600 PLC
27
TXV 138 08.02
$7FFF, underflow of the range is signalled by value $-7FFF ($8001). De-
tailed data on signalling of overflow and underflow of the range for individ-
ual types of inputs - see notes to table 5.1.
In the PID format, value of the input variable is passed, converted to the
format compatible with PID instructions of Tecomat programmable logic
controllers. The value can be interpreted as percentage expression of the
full measurement range. Exceeding of the range is signalled by the value
$7FFF. Detailed data on signalling exceeding of the range for individual in-
put types - see notes to table 5.1.
Tab. 5.1a. Format of input data of TC634 resistance temperature scanners
Data format
Scanner type/
FS
Technical units
PID
3
measurement range
tenths of
C
1)2)
tenths of
3
Pt100, W100 = 1.385
-200 to +850
C
0 to 65535
-2000 to +8500
Pt100, W100 = 1.391
-200 to +850
C
0 to 65535
-2000 to +8500
Ni1000, W100 = 1.617
-60 to +200
C
0 to 65535
-600 to +2000
Ni1000, W100 = 1.500
-60 to +200
C
0 to 65535
-600 to +2000
0 to 630
0 to 65535
0 to 6300
0 to 10000
0 to 2520
0 to 65535
0 to 25200
0 to 10000
1)
At conversion to the format of °C tenths, correction of non-linearity of
" # $%
(idt EN 60751:1995).
2)
For the marked format, value $7FFF signals interruption of the scanner,
value $-7FFF ($8001) signals short circuit of the scanner.
3)
For the marked format, exceeding of the upper limit of the range is sig-
nalled by value $7FFF.
Tab. 5.1b. Format of input data of TC634 current and voltage inputs
Data format
FS
Technical units
PID
Measurement
range
A
mV
tenths of
mV
0 to +20 mA
0 to 65535
0 to 20000
1)
0 to 10000
1)
+4 to +20 mA 0 to 65535
4000 to 20000
2)
0 to 10000
2)
0 to +10 V
0 to 65535
0 to 10000
3)
0 to 10000
3)
0 to +2 V
0 to 65535
0 to 20000
4)
0 to 10000
4)
1)
For the marked format, exceeding of the range at current higher than
22 mA is signalled.
2)
For the marked format, exceeding of the range at current higher than
22 mA is signalled, and underflow of the range at current lower than
3.5 mA.
3)
For the marked format, exceeding of the range at voltage higher than
10.1 V is signalled.
4)
For the marked format, exceeding of the range at voltage higher than
2.1 V is signalled.
Format PID
Format of input
data of resistance
temperature
scanners