![TECOM CHALLENGER User Manual Download Page 42](http://html1.mh-extra.com/html/tecom/challenger/challenger_user-manual_1072562042.webp)
42
V8-U-TXT.PM6 : Issue I , Revision I : October 1997
TEST INPUT
- Menu Option 12
This function is used to test an individual input device to determine if it is operating correctly.
The display will show:
Test Individual Input:
Input No:
ENTER
~
Return to the menu.
or
? ENTER
~
Test the selected input.
If you selected an input, one of four responses may be given:
a/ The input is sealed
eg.
SEALED On 12, Roller Door
Press ENTER
b/ The input is unsealed
eg.
UNSEALED On 12, Roller Door
Press ENTER
c/ There is a faulty condition due to cable tamper. The cabling to the input shows an OPEN circuit.
eg.
OPEN On 12, Roller Door
Press ENTER
d/ There is a faulty condition due to cable tamper. The cabling to the input shows a SHORT circuit.
eg
.
SHORT On 12, Roller Door
Press ENTER
From each of these displays:
ENTER
~
Return to the original menu option display.
Notes:
1.
If an input is unsealed, open or short, the console will emit a continuous tone. When the status of the input
is changed to sealed, the display will be updated and the tone will stop.
2.
If the input is isolated when a test is requested on it, the system will de-isolate the input, conduct the test
then return the input back to isolated.
3.
There is a pre-determined time in which to complete the test. If the test is not completed within this time,
the option is exited.
See Also:
Secure Test
Access Test
www.msealarms.com.au