Chapter 3 Notice for wiring
3.1 Precautions for Peripheral Applications
Power supply:
z
Make sure the voltage applied is correct to
avoid damaging the inverter.
z
A molded-case circuit breaker must be
installed between the AC source and the
inverter
Molded-case circuit breaker:
z
Use a molded-case circuit breaker that
conforms to the rated voltage and current of
the inverter to control the power ON/OFF and
protect the inverter.
z
Do not use the inverter as the switch for
run/stop switch.
Leakage breaker:
z
Install a leakage breaker to prevent error
operation caused by electric leakage and to
protect operators
z
Setting current should be 200mA or above and
the operating time at 0.1 second or longer to
prevent malfunction.
Magnetic contactor:
z
Normal operations do not need a magnetic
contactor. But a contactor has to be installed in
primary side when performing functions such
as external control and auto restart after power
failure, or when using brake controller.
z
Do not use the magnetic contactor as the
run/stop switch of the inverter.
AC reactor for power improvement:
z
When inverters below 200V/400V 15KW are
supplied with high capacity (above 600KVA)
power source or an AC reactor can be
connected to improve the power performance.
Install fast action fuse (If necessary):
z
To ensure the safety of peripheral devices,
please install the fast action fuse. Regarding
the specification, please refer to P7.
Input noise filter:
z
A filter must be installed when there are
inductive load around the inverter
Inverter:
z
Input power terminals L1, L2, and L3 can be
used in any sequence regardless of phases.
z
Output terminals T1, T2, and T3 are connected
to U, V, and W terminals of the motor. If the
motor is reversed while the inverter is forward,
just swap any two terminals of T1, T2, and T3.
z
To avoid damaging the inverter, do not connect
the input terminals T1, T2, and T3 to AC
power.
z
Connect the ground terminal properly. 200 V
series: class 3 grounding, <100
Ω
; 400 V
series : <10
Ω
.
Power
Molded-case
circuit breaker
Magnetic
contactor
AC reactor for
power
improvement
Install fast
action fuse
(If necessary)
Input noise
filter
CVP inverter
Ground
Three-phase
cage motor
Ground
Summary of Contents for JNTHBCBA0001BEAU
Page 1: ......
Page 51: ...49...
Page 53: ...51 0 1 z z z z 200V 100 400V 10 z z T1 U T2 V T3 W AC z CMOS IC z z...
Page 55: ...53 2 1 2 1 1 L1 L L2 L3 N T1 T2 T3 z z z 40 z IEC 61800 3 P57...
Page 56: ...54 2 1 2 CONNECTOR 2 1 3 5 2 1 4 z z z z z z z 5...
Page 57: ...55 2 1 5 10 40 95 RH 10 50 95 RH...
Page 70: ...68 4 2 15 16 17 PID 18 19 20...
Page 81: ...79 12 16 9 0 200 min 16 9 0 min Hi p Lo p 16 9 1BrE 19 3 16 9 1BrE 1BrE...
Page 82: ...80 13 17 0 P 0 0 10 0 rate 17 1 I 0 0 100 0 sec 17 2 D 0 00 10 00 sec P I D PID 18 0...
Page 84: ...82 16 17 7 0 0 10 0 sec 17 8 0 01 2 50 Bar 17 9 0 01 2 50 Bar 17 7 0 0 sec 17 7 17 8...
Page 93: ...91 32 20 A 0 1 2 3 4 5 PID FEEDBACK 20 B 0 200 TM2 0 10Vdc 20 A 20 B...
Page 96: ...94 5 2 L1 L L2 L3 N T1 T2 T3 T1 T2 T3 U V W AC...
Page 98: ......