41
When the output frequency of Master is over than 19-7(%) × 16-0, and 19-4 is
finished, or output frequency of Slave is less then 16-5 Sleep Frequency, and
persist time is bigger than 18-7 Sleep delay time, then Slave will get into sleep
mode.
Note: The 19-6/19-7 setting values of Master and Slave must be the same.
(28): 20-0 Run command source 0 : Keypad
1 : External Terminal
1.) 20-00 = 0 inverter is controlled by keypad.
2.) 20-00 = 1 When inverter is controlled by external terminal, the stop button on keypad
still enable for emergency stop.
(29): 20-1~20-5 S1~S5 Terminal Function
0 : Forward
1 : E.S. terminal A
2 : Base Block (b.b.)
3 : RESET
command
4 : Control signal switch
5 : Communication control signal switch
6 : PID
function disable
7 : Forced operating frequency
1.)
S1-S5 on TM2 are multi-function input terminals which can be set to the above
7 functions.
2.) 20-01~05
Function descriptions:
A. 20-01~05 = 0 Forward run
When forward command is on, motor will operate, when command is off,
motor will not operate.
B. 20-01~05 = 1 E.S. terminal A
When external E.S. is on, the drive will decelerate depend on the
Deceleration Time, and blink E.S. after stops. Please remove the E.S. signal
before turn the switch from off to on on (20-00=1) or press Run (20-00=0), then
the drive will operate from the starting frequency.
C. 20-01~05 = 2 Free run stop(Base block)
When Base block is on, the drive will block the PWM immediately and blink
“b.b.” on screen. After Base block command is removed, the drive will restart by
Speed search automatically.
D. 20-01~05 = 3 RESET
command
When terminal is on, reset the drive; off, does not work.
E. 20-01~05 = 4 Control signal switch
External control terminal off: operating signal is controlled by 20-00
External control terminal on: operating signal is controlled by Keypad
display.
Summary of Contents for JNTHBCBA0001BEAU
Page 1: ......
Page 51: ...49...
Page 53: ...51 0 1 z z z z 200V 100 400V 10 z z T1 U T2 V T3 W AC z CMOS IC z z...
Page 55: ...53 2 1 2 1 1 L1 L L2 L3 N T1 T2 T3 z z z 40 z IEC 61800 3 P57...
Page 56: ...54 2 1 2 CONNECTOR 2 1 3 5 2 1 4 z z z z z z z 5...
Page 57: ...55 2 1 5 10 40 95 RH 10 50 95 RH...
Page 70: ...68 4 2 15 16 17 PID 18 19 20...
Page 81: ...79 12 16 9 0 200 min 16 9 0 min Hi p Lo p 16 9 1BrE 19 3 16 9 1BrE 1BrE...
Page 82: ...80 13 17 0 P 0 0 10 0 rate 17 1 I 0 0 100 0 sec 17 2 D 0 00 10 00 sec P I D PID 18 0...
Page 84: ...82 16 17 7 0 0 10 0 sec 17 8 0 01 2 50 Bar 17 9 0 01 2 50 Bar 17 7 0 0 sec 17 7 17 8...
Page 93: ...91 32 20 A 0 1 2 3 4 5 PID FEEDBACK 20 B 0 200 TM2 0 10Vdc 20 A 20 B...
Page 96: ...94 5 2 L1 L L2 L3 N T1 T2 T3 T1 T2 T3 U V W AC...
Page 98: ......