Pressure
Feedback
18-0
Target Pressure Value
18-8
Sleep Tolerance Range
Output
Frequency
Output
Frequency
A
B
C
D
19-4
Launch
Delay Time
A : When dual pump operate, Master start and Slave(1~3) is standing by, then system is
operating in the constant pressure.
B : When water usage become larger, then the output frequency of Master will increase.
If the feedback pressure does not reach setting range of 18-8(Sleep Tolerance
Pressure ) and 19-4(Launch Delay Time) is not finished, Slave is still standing by.
C : When 19-4 is finished, Master request Slave to operate simultaneously to keep
constant pressure. If water usage reduced, the output frequency will decrease.