4-97
12 Monitor Parameters
12-00
Display Mode
Range
0 0 0 0 0
MSD LSD
00000~88888 Each digit can be set from 0 to 8 as listed below.
【
0
】
:Disable display(frequency& parameters)
【
1
】
:output Current
【
2
】
:output Voltage
【
3
】
:DC voltage
【
4
】
:Temperature
【
5
】
:PID feedback
【
6
】
:AI1
【
7
】
:AI2
【
8
】
:Count Status
Note:
The highest bit is used for power-up monitor. The 4 least significant bits can be used to customize the
display sequence see chapter 4.1.3.
12-01
PID Feedback Display format
Range
【
0
】
:Displayed in Integer (xxx)
【
1
】
:One Decimal Place (xx.x)
【
2
】
:Two Decimal Places (x.xx)
12-02
PID Feedback Display Unit Setting
Range
【
0
】
:xxx--
【
1
】
:xxxpb(pressure)
【
2
】
:xxxfl(flow)
12-03
Custom Units (Line Speed) Display Mode
Range
【
0~65535
】
Rpm
Set motor rated RPM for the inverter to display the actual motor speed based on the output frequency.
Motor synchronous speed = 120 x Rated frequency ÷ Number of poles.
12-04
Custom Units (Line Speed) Display Mode
Range
【
0
】
:Drive Output Frequency is Displayed
【
1
】
:Line Speed is Displayed in Integer (xxxxx)
【
2
】
:Line Speed is Displayed with One Decimal Place (xxxx.x)
【
3
】
:Line Speed is Displayed with Two Decimal Places (xxx.xx)
【
4
】
:Line Speed is Displayed with Three Decimal Places (xx.xxx)
12-
04≠0,
line speed is displayed while the inverter is running or stopped.