4-48
Notes:
-
To enable Fire Mode function set parameter 08-17 = 1
-
The fire Mode function is activated by using one of the multifunction inputs S1 to S6 to a value of 28.
(Parameter 03-00~03-05).
- Fire mode can also be enabled by setting the functions of S1 to S6 via communication.
When Fire Mode is active:
- The keypad shows FIrE, and Fire Mode activation is recorded in the inverter fault log.
- The inverter will run up to the maximum frequency set in 00-12.
- The inverter will keep running unless main power is lost or the inverter breaks down.
- When Fire Mode is activated, all protection functions and alarms
(e.g. ES, BB, OV, OC …), will be ignored.
- STOP key on the keypad is disabled during Fire Mode operation.
- To reset fire mode: turn power off, remove fire mode input signal, and power-up inverter.
03-06
Up/Down Frequency Step
Range
【
0.00~5.00
】
Hz
Example: S1: 03-00=
【
8
】
Up
frequency command, S2: 03-01=
【
9
】
Down
frequency command,
03-06=
【
△
】
Hz
Mode1:
UP or DOWN input terminals are turned on for less than 2 sec. The operation frequency changes by
△
Hz (03-06) each time the input terminal is closed.
Mode 2:
If UP or DOWN input terminals are closed for more than 2 sec, the original UP/DOWN mode is active
and the output frequency ramps up or down as long as the input is kept ON.
S1
S2
ON
ON
ON
Hz
T
△
Hz
Actual output
frequency
ON
ON
ON