4-22
Group 10: PID Parameters
No.
Description
Range
Factory
Setting
Unit
Note
10-22
Min PID Feedback Setting Level
0 ~999
0
-
*1
Group 11: Auxilary Parameters
No.
Description
Range
Factory
Setting
unit
Note
11-00
Reverse Operation Control
0: Reverse Command is Enabled
1: Reverse Command is Disabled
0
-
11-01
Carrier Frequency (kHz)
1~16
5
KHz
11-02
Carrier Mode Selection
0: Mode0, 3Phase PWM modulation
1: Mode1, 2Phase PWM modulation
2: Mode2, 2Phase Random PWM Modulation
0
-
11-03
Carrier Frequency
Reduction by Temperature Rise
0:Disable
1:Enable
0
-
11-04
S-Curve Acc 1
0.0 ~ 4.0
0.2
Sec
11-05
S-Curve Acc 2
0.0 ~ 4.0
0.2
Sec
11-06
S-Curve Dec 3
0.0 ~ 4.0
0.2
Sec
11-07
S-Curve Dec 4
0.0 ~ 4.0
0.2
Sec
11-08
Skip Frequency 1
0.00 ~ 650.00
0.00
Hz
*1
11-09
Skip Frequency 2
0.00 ~ 650.00
0.00
Hz
*1
11-10
Skip Frequency 3
0.00 ~ 650.00
0.00
Hz
*1
11-11
Skip Frequency Range
Bandwith (±)
0.00 ~ 30.00
0.00
Hz
*1
11-12
Energy Saving Gain (V/F Mode)
0 ~ 100
80
%
11-13
Regeneration Prevention Function
0:Disable
0
-
1:Enable
2:Enable (only during constant speed)
11-14
Regeneration Prevention Voltage
Level
200V:300.0~400.0
380.0
V
400V:600.0~800.0
760.0
11-15
Regeneration Prevention
Frequency Limit
0.00 ~ 15.00
3.00
Hz
11-16
Regeneration Prevention Voltage
Gain
0~200
100
%
11-17
Regeneration Prevention
Frequency Gain
0~200
100
%