4-55
03-22
Pre-set count 1
Range
【
0~9999
】
03-23
Pre-set count 2
Range
【
0~9999
】
The internal counter function can be used to count external pulses and activate RY1 & RY2 output relays to
indicate pre-set count has been reached set in parameters 03-22 & 03-23.
Internal counter counts can be checked against a single preset value or a both pre-set values.
S
ingle pre-set count
Set parameter 03-22 to the required pre-set count.
To activate relays RY1 or RY2 for a single pre-set count set parameter 03-11 (RY1) or 03-12 (RY2) as required
to 16.
Pulse inputs at the selected terminal will increment the internal counter until the pre-set count in parameter
03-22 is reached and the selected Ry1 or Ry2 relay is
turned ON.
Removing the input signal when the pre-set count is reached will reset counter to zero and the selected relay is
turned OFF.
Dual pre-set count
Set 03-23 to
turn ON
the selected relay and Set parameter 03-22 to
turn OFF
the selected Relay.
To activate relays RY1 or RY2 for a Dual pre-set count set parameter 03-11 (RY1) or 03-12 (RY2) as required
to 17.
Pulse inputs at the selected terminal increments the internal counter until the pre-set count in parameter 03-23
is reached and the selected RY1 or RYy2 relay is turned
ON. When pulse counter reaches the pre-set count set
in parameter 03-22 is reached RY1 or RY2 relay is turned
OFF.
Removing the input signal when the pre-set count is reached will reset counter to zero and the selected relay is
turned OFF.
03-22 pre-set value must be greater than pre-set value of 03-23.
Example:
Single and dual preset counts using RY1 and RY2
Count display
set by
parameter
12-00=00008
Dual preset-count set by parameter 03-11=17
(RY1) and 03-22=4 , 03-23=2
Single preset-count set by parameter 03-12=16
(RY2) 03-22=4
>= 2ms
C0001
C0002
C0003
C0004
C0001
C0002
C0000
C0003