2) F11 - F15=005: Jog Frequency Command
The
e
xternal input terminal set to Jog operation. When turned ON, the inverter will run at the Jog
frequency, F36.
Parameter
Description
Frequency range
Factory default
F28
Preset frequency 1 (Hz)
00.0 - 200
05.0
F29
Preset frequency 2 (Hz)
00.0 - 200
05.0
F30
Preset frequency 3 (Hz)
00.0 - 200
10.0
F31
Preset frequency 4 (Hz)
00.0 - 200
20.0
F32
Preset frequency 5 (Hz)
00.0 - 200
30.0
F33
Preset frequency 6 (Hz)
00.0 - 200
40.0
F34
Preset frequency 7 (Hz)
00.0 - 200
50.0
F35
Preset frequency 8 (Hz)
00.0 - 200
60.0
F36
Jog frequency (Hz)
00.0 - 200
05.0
Set
f
requency priority: Jog→ Preset frequency →External analog frequency signal
Preset
Frequency
Command 3
Set value =004
Preset
Frequency
Command 2
Set value =003
Preset
Frequency
Command 1
Set value =002
Jog frequency
Command
Set value =005
Output
frequency
0
0
0
0
F28
0
0
1
0
F29
0
1
0
0
F30
0
1
1
0
F31
1
0
0
0
F32
1
0
1
0
F33
1
1
0
0
F34
1
1
1
0
F35
X
X
X
1
F36
X = 1 or 0
F37 DC braking time (s) : 00.0 - 25.5
F38 DC braking start frequency (Hz) : 01.0 - 10.0
F39 DC braking level (%) : 00.0 - 20.0%
(Level 100% based on Motor Rate Voltage F44)
NOTE: DC braking is enabled / disabled by multifunction input setting as described on page 33
F37 / F38: DC braking time and start frequency, per the following figure:
F38
HZ
t
F37
Fig. 11.7 DC Injection Braking
t
t
F38
HZ
TM2
DC
Brake
Signal
F11
–
F15=019