EV Inverter Operating Manual
___________________________________________________________________________
TECO
– Westinghouse Motor Company 28
1.) F5=001: When any parameter F11- F15 is set to 015 and the multi-function input terminal is
OFF, the frequency is set by the potentiometer on the keypad. If the multi-function input
terminal is ON, the frequency is set by the analog signal (AIN) from TM2.
2.) F5=002: When any parameter F11 - F15 is set to 015 and the multi-function input terminal is
OFF, the frequency is set by the analog signal (AIN) from TM2. If the multi-function input
terminal ON, the frequency is set by the potentiometer on the keypad.
3.) F5=003: Up / Down terminal: Refer to the description of parameters F11- F15 (multi-function
input terminal).
4.) Priority of frequency command; Jog> preset frequency > (k
eypad▲▼ or TM2 Up / down or
communication)
F06 External control operation mode
000: Forward / Stop
– Reverse / Stop
001: Run / Stop - Forward / Reverse
002: 3-wire
—Run / Stop
1.) F06 is only available when F04 = 001 (TM2 terminal).
2.) When both forward and reverse commands are ON, this will result in a stopped mod
e.
S1 (Run)
S2 (Stop)
S3 (Forward / Reverse)
+24V (Common)
(2) PNP Input Signal
S1 (Run)
S2 (Stop)
S3 (Forward / Reverse)
COM (Common)
(1) NPN Input Signal
Parameter F06 = 002, control method works as follows:
S1 (Run)
S2 (Forward / Reverse)
+24V (Common)
(2) PNP Input Signal
Fig. 11.1c 3- Wire Run / Stop
Fig. 11.1b Run / Stop – Forward / Reverse
S1 (Run)
S2 (Forward / Reverse)
COM (Common)
(1) NPN Input Signal
Parameter F06 = 001, control method works as follows:
Fig. 11.1a Forward / Stop – Reverse / Stop
S1 (Forward / Stop)
S2 (Reverse / Stop)
+24V (Common)
(2) PNP Input Signal
S1 (Forward / Stop)
S2 (Reverse / Stop)
COM (Common)
(1) NPN Input Signal
Parameter F06 = 000, control method works as follows:
NOTE: In 3 wire control mode, terminals S1-S3 are dedicated, therefore
parameters F11
-
F13 are ineffective.