background image

ENGLISH 

UPS EVO DSP PLUS 1.2-2.4-3.6 MM 

13

 

User’s manual 

 

 

If  neutral  line  and  ground  line  are  short  circuited,  please  add  isolation  transformer 
between UPS and devices. See the image below. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Never  connect  neutral  line  of  input  to  neutral  line  of  output.  Otherwise,  it  will  cause 
the damage of the UPS. See the image below. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

6.1

 

Installation  

 

We advise you to follow the steps below explained: 

1.

 

Through  the  included  power  cable  connect  the  UPS  Input  socket  to  the  AC  line  outlet  (see  figure  4). 

It  is 

mandatory to ground the AC line outlet according to the Safety Standards

. Carefully check the grounding 

of AC line outlet.  

2.

 

Connect  the  devices  to  be  supplied  to  the  UPS  outputs,  by  using  only  the  included  cables.  Be  sure  all  the 
devices have the main switch in OFF position. 

DEVICE 

LINE 

NEUTRAL 

GND 

LINE 

NEUTRAL 

LINE 

NEUTRAL 

UPS 

ISOLATION 

TRANSFORMER 

INPUT 

OUTPUT 

LINE 

NEUTRAL 

LINE 

NEUTRAL 

UPS 

Summary of Contents for EVO DSP PLUS MM 1.2

Page 1: ...Uninterruptible Power Supply EVO DSP PLUS MM 1 2 EVO DSP PLUS MM 2 4 EVO DSP PLUS MM 3 6 User s manual Manuale utente...

Page 2: ...m 11 5 2 Rear Side 11 6 Electrical Installation 12 6 1 Installation 13 7 First Start Up 14 8 Functioning 15 8 1 Turning ON and OFF 15 8 2 Low Battery and Automatic Restart 15 8 3 Load Testing 16 8 4 S...

Page 3: ...el authorized by producer TECNOWARE declines any responsibility if this warning is disregarded The electric installation has to be done by qualified personnel Follow all the Safety Standards CEI Stand...

Page 4: ...DSP PLUS MM protects the devices from accidental overload or Inverter fault by an Automatic Bypass that directly connects the AC Input line with its outlets EVO DSP PLUS MM models are factory equipped...

Page 5: ...s of all the UPS parameters by user through front panel pushbuttons and graphic LCD panel SNMP Adapter optional Communication with the computer through USB interfaces ECO functioning mode selectable F...

Page 6: ...o leave at least 10 cm of unobstructed space all around the UPS in order to keep it properly ventilated Do not obstruct ventilation holes Do not insert objects or pour liquids in the ventilation holes...

Page 7: ...if the UPS finds the Mains OFF condition due to a Blackout or Overvoltage Brownout it then switches into Battery mode In this case the batteries supply the required Output power thanks to the DC AC c...

Page 8: ...mpletely off The Stand by mode is identified by The graphic LCD panel shows the path of energy flow during Stand by mode 4 5 ECO Mode It is possible to select the ECO mode to save energy and to increa...

Page 9: ...quency by default the Converter Frequency mode is disable The Converter Frequency mode is identified by The graphic LCD panel shows the path of energy flow during Converter Frequency mode The CF chara...

Page 10: ...DSP PLUS 1 2 2 4 3 6 MM 5 1 1 Graphic LCD Panel Please refer to figure 3 Figure 3 Graphic LCD Panel Battery Info Mode Operation Info Input Battery Voltage Info Output Voltage Info Load Info Backup Ti...

Page 11: ...n Indicates that the UPS alarm is disabled muted Output Voltage information Indicates the Output Voltage or Frequency Vac Output Voltage Hz Output Frequency Load information Indicates the load level b...

Page 12: ...for at least 5 seconds to perform the Battery Test while the UPS is in Normal mode SELECT Select the measurements on the graphic display by pressing the SELECT button it is possible to choose the ele...

Page 13: ...n RJ11 RJ45 IN OUT connectors to protect and filter a phone line an ADSL or a LAN TNV 3 type connections 4 Grounded AC Input power socket IEC C14 type for EVO DSP PLUS 1 2 2 4 MM and IEC C20 type for...

Page 14: ...t connections use ONLY the included power cables or cables with the same power ratings TECNOWARE declines any responsibility if this warning is disregarded The EVO DSP PLUS MM models are made of a sin...

Page 15: ...se you to follow the steps below explained 1 Through the included power cable connect the UPS Input socket to the AC line outlet see figure 4 It is mandatory to ground the AC line outlet according to...

Page 16: ...connected to the UPS outputs have the main switch in OFF position 2 Restore the AC Input line for the UPS be sure that the AC utility power is available and that its voltage and frequency are within t...

Page 17: ...ss the OFF button If the ON button is pressed when AC Input line is not present the UPS switches ON even and works in Battery mode after some seconds If the OFF button is pressed when AC Input line is...

Page 18: ...condition Do not connect a load greater than rated value to the UPS see POWER specifications in the chapter Technical Characteristics as this may damage the unit In this case the warranty is void 8 4...

Page 19: ...ning condition the buzzer beeps once every second it means that there are some problems for UPS operation Users can get the Fault code from graphic LCD panel Please check the Troubleshooting chapter f...

Page 20: ...circuit 14 Vdc Bus Under 03 None Battery Voltage too High 27 Vdc Bus Unbalance 04 None Battery Voltage too Low 28 Inverter Soft Start failure 11 None Over Temperature 41 None High Inverter Voltage 12...

Page 21: ...imit come back to Line mode 290 Vac 5 Nominal Frequency 50 60 Hz automatic selection Frequency Range Normal mode 47 53 Hz 57 63 Hz Input Power Factor 0 99 at 100 Load OUTPUT Nominal Voltage Single Pha...

Page 22: ...without Derating 3000 m Protection level IP 20 Cooling Fan cooling Audible Noise at 1 meter 45 dBA STANDARDS Safety EN 62040 1 1 EN 60950 1 Performance EN 62040 3 EMC EN 62040 2 category C2 Product c...

Page 23: ...lly if the UPS is ON and working in Normal or in Bypass mode for after approximately 4 hours with AC Input line present Battery life strongly depends on the ambient temperature There are also other fa...

Page 24: ...rviceable Any repair or maintenance work must be performed exclusively by qualified technical personnel authorized by TECNOWARE TECNOWARE declines any responsibility if this warning is disregarded SYM...

Page 25: ...Fault code is shown as 14 the icon lights on LCD display and alarm beeps continuously The UPS shuts down automatically because short circuit occurs on the UPS Output Check Output wiring or if connect...

Page 26: ...al or an improper use of the same or of any parts can be damaging for the environment and for human health A correct waste disposal of products having the dustbin symbol marked by a cross help to avoi...

Reviews: