Low DC cut-off voltage
If user-defined is selected in program 5, this program can be set
up. Setting range is from 40.0V to 48.0V and increment of each
click is 0.1V. Low DC cut-off voltage will be fixed to setting value
no matter what percentage of load is connected. Then, low DC
warning voltage is 2V higher than cut-off voltage, low DC warning
return voltage is 4V higher than cut-off voltage and Cold Start
Voltage is 4V higher than cut-off voltage.
31
Solar power balance:
When enabled, solar input
power will be automatically
adjusted according to
connected load power.
(Only available for
4KVA/5KVA model)
“Solar Power Balance”
enable
(default)
:
If selected, solar input power will be
automatically adjusted according to
the following formula:
Max. input solar power = Max.
battery charging power + Connected
load power.
“Solar Power Balance”
disable:
If selected, the solar input power
will be the same to max. battery
charging power no matter how much
loads are connected. The max.
battery charging power will be based
on the setting current in program
02.
(Max. solar power = Max. battery
charging power)