background image

GB

11

LOWER THAN 750 µS/cm.

The humidifier gets to the real working level
slowly, as it takes some hours (sometimes
some days) to make the water evaporate as to
concentrate the salts inside of the cylinder, so
the water can get to a conductivity higher than
750 µS/cm.

SWITCH > AUTOMATIC POSITION

(AUT)

SWITCH > AUTOMATIC POSITION

(MAX)

IMPORTANT

(fig. 8)

SWITCH TO CHOOSE HUMIDIFICATION
POWER.
In “AUT” position the system supplies 30% of
max. water vapour delivery which is preset in
phases Iª and IIª of LevControl 1; Iª, IIª, IIIª of
LevControl 2. It supplies the max. water vapour
delivery in phase IIIª of LevControl 1 and in
phase IVª of Lev Control 2.
In “MAX” position it always supplied the maw.
water vapour delivery.

Note: The “MAX” position must be used
only during the manual leavening phase.

W

W

W

W

A

A

A

A

R

R

R

R

N

N

N

N

II

II

N

N

N

N

G

G

G

G

!!

!!

!!

!!

!!

!!

THE USER MUST NOT INTERVENE SHOULD ANY OF THE FOLLOWING MACHINE MAL-
FUNCTIONS OCCUR.
IT IS OBLIGATORY TO CONTACT AN AUTHORIZED TECNOMAC TECHNICIAN.

1.  THE CONTROL PANEL IS NOT WORKING
2.  THE HEATING SYSTEM IS NOT WORKING
3.  IN ANY OTHER CASE OF IRREGULAR FUNCTIONING

4.  PERIODIC MAINTENANCE

W

W

W

W

A

A

A

A

R

R

R

R

N

N

N

N

II

II

N

N

N

N

G

G

G

G

!!

!!

!!

!!

!!

!!

THIS PROCEDURE MAY ONLY BE DONE

BY AN AUTHORISED TECNOMAC

INSTALLATION TECHNICIAN

STEAM BOILER UNIT

Maintenance is advisable any time you the
humidifier after a long period of inaction or
when the “worn-out cylinder” alarm appears. In
such a case it is necessary to remove and
replace the cylinder, the only component sub-
ject to deterioration. If the humidifier operates
particularly with hard or aggressive water, it
should be necessary to substitute the cylinder

more frequently. Don't use decalcifiers or any
type of acids to wash the cylinder, as to avoid
the corrosion of the internal parts.
Remove the cylinder as follows:
– Empty the cylinder, draining water through

the “DR” key;

– Power supply OFF;
– Disconnect the steam pipe from the cylinder;
– Disconnect the electric connections to the

Summary of Contents for T 93 E H2

Page 1: ...AUT MAX AUT MAX Cod 71503070 0 12 97 OUR SYSTEMS CONFORM TO EC STANDARD 73 23 CEE 89 336 INSTRUCTION MANUAL GB S T E A M H U M I D I F I E R S T 93 E H2 T 97 E H3 ...

Page 2: ...TS 6 DISASSEMBLY OF MACHINE AND OR COMPONENTS 7 ADJUSTMENT AND SETTING PROCEDURES 8 MACHINE CLEANING AND MAINTENANCE RELATIVE TO THE FOLLOWING PARTS AND COMPONENTS ELECTRICAL ELECTRONIC MECHANICAL W W W WA A A AR R R RN N N NI I I IN N N NG G G G MACHINE USER IS SVERELY PROHIBITED FROM CARRYING OUT THE OPERATIONS MARKED WITH THIS SYMBOL ...

Page 3: ...res the best operation of the humidifi er in relation to the chemical characteristics of the feeding water On the top of the cylinder there are two small high level electrodes E they measure the water level and if it exceeds the maximum selected value water is dis charged through the relative discharge pipe The controller will instruct the drain solenoid valve S to open close on the basis of the f...

Page 4: ... having car ried out the necessary connections hydraulic and electric and after having connected it to a humidistat regulator or probe The humidifiers are started by pressing the switch Wait just a few seconds for the initial test to take place After that THE CONTROLLER WITH LEDSs AND PUSHBUTTONs will turn ON the capacity led indicators Tecnomac garantees the working of its own humidifiers only if...

Page 5: ...E FOLLOWING MACHINE MAL FUNCTIONS OCCUR IT IS OBLIGATORY TO CONTACT AN AUTHORIZED TECNOMAC TECHNICIAN 1 THE CONTROL PANEL IS NOT WORKING 2 THE HEATING SYSTEM IS NOT WORKING 3 IN ANY OTHER CASE OF IRREGULAR FUNCTIONING 4 PERIODIC MAINTENANCE W W W WA A A AR R R RN N N NI I I IN N N NG G G G THIS PROCEDURE MAY ONLY BE DONE BY AN AUTHORISED TECNOMAC INSTALLATION TECHNICIAN STEAM BOILER UNIT Maintenan...

Page 6: ...DS FILL AND DRAIN SOLENOID VALVES Disconnect the power supply leads Remove the fill drain solenoid valve Remove any possible salt deposits under a jet of water Check the conditions of the flow sensor with in the fill solenoid valve don t use com pressed air as to avoid damages to the flow regulator Refit the valves and power the humidifier DRAINAGE AND STEAM CONVEYANCE PIPINGS These pipes may get ...

Reviews: