1.  GENERAL FEATURES ON STEAM HUMIDIFIERS

FUNCTION LOGIC

It is possible to create a flow of electric current
by simply applying tension to two electrodes
immersed into a water container. This makes
the water boil. In fact, water containing just a
very small quantity of salts, behaves as if it
were an electric resistance and closes the cir-
cuit between the two electrodes.

MAIN PARTS

Any steam requirement is controlled by the
electronic controller (R). It energises thecon-
tactor to supply power to the immersed elec-
trodes. Steam production is indicated on the
control display and the absorbed energy is
controlled by the current transformer (TAM).
When steam production drops below the set
value following a decrease of water level, the
controller instructs the solenoid valve (C) to fill
the charge tank (V) so as to allow water to flow
into the boiler by gravity.
The fill tank has two electrodes which measure
the conductivity of the feed water.
The ensures the best operation of the humidifi-
er in relation to the chemical characteristics of
the feeding water. On the top of the cylinder
there are two small high level electrodes (E):
they measure the water level and if it exceeds
the maximum selected value, water is dis-
charged through the relative discharge pipe.
The controller will instruct the drain solenoid
valve (S) to open/close on the basis of the
feeding water chemical characteristics. This

serves to maintain the best concentration of
salts within the cylinder and ensures the cor-
rect functioning of the humidifier.

(fig. 1 e 2)

V - Feed tank with  electrodes for conductivity

measurement

E - Top level electrodes
T - Overflow pipe
B - Cylinder boiler
C - Feed valve
S - Discharge valve
R - Electronic control panel

ELECTRONIC CONTROLLER

The compact OEM humidifier is equipped with
the new microprocessor-based controller CDA
303.
The controller has a current transformer as well
as the operative contacts for the single-phase
function mode.

TECHNICAL CHARACTERISTICS T 93 e H2 T97 e H3

Production

Kg./h

3

3

Electrical absorption

amper

9,9

3,3

Power

kw

2,17

Feeding current

220/V/50 HZ

380/V/50 HZ

Monophase

xxxxxxx

Summary of Contents for T 93 E H2

Page 1: ...AUT MAX AUT MAX Cod 71503070 0 12 97 OUR SYSTEMS CONFORM TO EC STANDARD 73 23 CEE 89 336 INSTRUCTION MANUAL GB S T E A M H U M I D I F I E R S T 93 E H2 T 97 E H3 ...

Page 2: ...TS 6 DISASSEMBLY OF MACHINE AND OR COMPONENTS 7 ADJUSTMENT AND SETTING PROCEDURES 8 MACHINE CLEANING AND MAINTENANCE RELATIVE TO THE FOLLOWING PARTS AND COMPONENTS ELECTRICAL ELECTRONIC MECHANICAL W W W WA A A AR R R RN N N NI I I IN N N NG G G G MACHINE USER IS SVERELY PROHIBITED FROM CARRYING OUT THE OPERATIONS MARKED WITH THIS SYMBOL ...

Page 3: ...res the best operation of the humidifi er in relation to the chemical characteristics of the feeding water On the top of the cylinder there are two small high level electrodes E they measure the water level and if it exceeds the maximum selected value water is dis charged through the relative discharge pipe The controller will instruct the drain solenoid valve S to open close on the basis of the f...

Page 4: ... having car ried out the necessary connections hydraulic and electric and after having connected it to a humidistat regulator or probe The humidifiers are started by pressing the switch Wait just a few seconds for the initial test to take place After that THE CONTROLLER WITH LEDSs AND PUSHBUTTONs will turn ON the capacity led indicators Tecnomac garantees the working of its own humidifiers only if...

Page 5: ...E FOLLOWING MACHINE MAL FUNCTIONS OCCUR IT IS OBLIGATORY TO CONTACT AN AUTHORIZED TECNOMAC TECHNICIAN 1 THE CONTROL PANEL IS NOT WORKING 2 THE HEATING SYSTEM IS NOT WORKING 3 IN ANY OTHER CASE OF IRREGULAR FUNCTIONING 4 PERIODIC MAINTENANCE W W W WA A A AR R R RN N N NI I I IN N N NG G G G THIS PROCEDURE MAY ONLY BE DONE BY AN AUTHORISED TECNOMAC INSTALLATION TECHNICIAN STEAM BOILER UNIT Maintenan...

Page 6: ...DS FILL AND DRAIN SOLENOID VALVES Disconnect the power supply leads Remove the fill drain solenoid valve Remove any possible salt deposits under a jet of water Check the conditions of the flow sensor with in the fill solenoid valve don t use com pressed air as to avoid damages to the flow regulator Refit the valves and power the humidifier DRAINAGE AND STEAM CONVEYANCE PIPINGS These pipes may get ...

Reviews: