10
2. SETTING UP
W
W
W
W
A
A
A
A
R
R
R
R
N
N
N
N
II
II
N
N
N
N
G
G
G
G
!!
!!
!!
!!
!!
!!
THIS PROCEDURE MAY ONLY BE DONE
BY AN AUTHORISED TECNOMAC
INSTALLATION TECHNICIAN
Setting up the humidifier requires hydraulic
connections tho the fill and drain valve.
FEEDING PIPE
The feeding water will be conveyed from the
water-gate valve and pipework (min.) 6 mm.
internal diameter.
Please Note that pressure ranges between 1
and 10 bars. In case of higher pressure values
it will be necessary to use a pressure reducer
set at 3-4 bars. The feeding water temperature
must not go above 50°C.
IMPORTANT: Use water coming from the
city water mains. DO NOT USE TREATED
WATER (demineralized, soft, deionized
water).
If the feeding water contains dirt or impurities,
it is advisable to use a filter to improve the
quality of water. There is a series of water filters
available, forfiltering particles from 1 to 5 µm.
For fur ther infor mation please contact
Tecnomac Service.
3. START-UP PROCEDURES
HUMIDIFIER START-UP
The humidifier can be started after having car-
ried out the necessary connections (hydraulic
and electric) and after having connected it to a
humidistat, regulator or probe.
The humidifiers are started by pressing the
switch.
Wait just a few seconds for the initial test to
take place.
After that:
THE CONTROLLER WITH LEDSs AND
PUSHBUTTONs will:
turn ON the capacity led indicators.
Tecnomac garantees the working of its own
humidifiers only if they are connected to the
water network (not softned, not be, ineralised,
not treated with any kind of thing) with conduc-
tivity between 125 and 1250 µS/cm.
There are two different starting procedures,
depending on the water conductivity:
FEEDING WATER WITH CONDUCTIBILITY
HIGHER THAN 750 µS/cm.
The humidifier reaches full efficiency immedi-
ately, adjusting water flow to the cylinder to
provide the value of current necessary to pro-
duce the required steam quantity.
FEEDING WATER WITH CONDUCTIBILITY
FEEDING PIPE
Min. internal dia. feeding pipe (mm)
Mains pressure (bar)
Max. capacity feeding water (I/min)
Feeding water temperature
Feeding water connection
DISCHARGE
Discharge water connection (mm)
Min. dia. discharge pipe (mm)
STEAM CONVEYANCE
Pipe diameter (mm)
6
1-10
0,6
50°C
3/4” G(M)
30
3/4” G(F)
25
T 93 E H2 - T 97 E H3