2. SETTING UP

W

W

W

W

A

A

A

A

R

R

R

R

N

N

N

N

II

II

N

N

N

N

G

G

G

G

!!

!!

!!

!!

!!

!!

THIS PROCEDURE MAY ONLY BE DONE

BY AN AUTHORISED TECNOMAC

INSTALLATION TECHNICIAN

Setting up the humidifier requires hydraulic
connections tho the fill and drain valve.

FEEDING PIPE

The feeding water will be conveyed from the
water-gate valve and pipework (min.) 6 mm.
internal diameter.
Please Note that pressure ranges between 1
and 10 bars. In case of higher pressure values
it will be necessary to use a pressure reducer
set at 3-4 bars. The feeding water temperature
must not go above 50°C.

IMPORTANT: Use water coming from the
city water mains. DO NOT USE TREATED
WATER (demineralized, soft, deionized
water).

If the feeding water contains dirt or impurities,
it is advisable to use a filter to improve the

quality of water. There is a series of water filters
available, forfiltering particles from 1 to 5 µm.
For fur ther infor mation please contact
Tecnomac Service.

3. START-UP PROCEDURES

HUMIDIFIER START-UP

The humidifier can be started after having car-
ried out the necessary connections (hydraulic
and electric) and after having connected it to a
humidistat, regulator or probe.
The humidifiers are started by pressing the
switch.
Wait just a few seconds for the initial test to
take place.
After that:

THE CONTROLLER WITH LEDSs AND
PUSHBUTTONs will:

turn ON the capacity led indicators.

Tecnomac garantees the working of its own
humidifiers only if they are connected to the
water network (not softned, not be, ineralised,
not treated with any kind of thing) with conduc-
tivity between 125 and 1250 µS/cm.

There are two different starting procedures,
depending on the water conductivity:

FEEDING WATER WITH CONDUCTIBILITY
HIGHER THAN 750 µS/cm.

The humidifier reaches full efficiency immedi-
ately, adjusting water flow to the cylinder to
provide the value of current necessary to pro-
duce the required steam quantity.

FEEDING WATER WITH CONDUCTIBILITY

FEEDING PIPE

Min. internal dia. feeding pipe (mm)

Mains pressure (bar)

Max. capacity feeding water (I/min)

Feeding water temperature

Feeding water connection

DISCHARGE

Discharge water connection (mm)

Min. dia. discharge pipe (mm)

STEAM CONVEYANCE

Pipe diameter (mm)

6

1-10

0,6

50°C

3/4” G(M)

30

3/4” G(F)

25

T 93 E H2 - T 97 E H3

Summary of Contents for T 93 E H2

Page 1: ...AUT MAX AUT MAX Cod 71503070 0 12 97 OUR SYSTEMS CONFORM TO EC STANDARD 73 23 CEE 89 336 INSTRUCTION MANUAL GB S T E A M H U M I D I F I E R S T 93 E H2 T 97 E H3 ...

Page 2: ...TS 6 DISASSEMBLY OF MACHINE AND OR COMPONENTS 7 ADJUSTMENT AND SETTING PROCEDURES 8 MACHINE CLEANING AND MAINTENANCE RELATIVE TO THE FOLLOWING PARTS AND COMPONENTS ELECTRICAL ELECTRONIC MECHANICAL W W W WA A A AR R R RN N N NI I I IN N N NG G G G MACHINE USER IS SVERELY PROHIBITED FROM CARRYING OUT THE OPERATIONS MARKED WITH THIS SYMBOL ...

Page 3: ...res the best operation of the humidifi er in relation to the chemical characteristics of the feeding water On the top of the cylinder there are two small high level electrodes E they measure the water level and if it exceeds the maximum selected value water is dis charged through the relative discharge pipe The controller will instruct the drain solenoid valve S to open close on the basis of the f...

Page 4: ... having car ried out the necessary connections hydraulic and electric and after having connected it to a humidistat regulator or probe The humidifiers are started by pressing the switch Wait just a few seconds for the initial test to take place After that THE CONTROLLER WITH LEDSs AND PUSHBUTTONs will turn ON the capacity led indicators Tecnomac garantees the working of its own humidifiers only if...

Page 5: ...E FOLLOWING MACHINE MAL FUNCTIONS OCCUR IT IS OBLIGATORY TO CONTACT AN AUTHORIZED TECNOMAC TECHNICIAN 1 THE CONTROL PANEL IS NOT WORKING 2 THE HEATING SYSTEM IS NOT WORKING 3 IN ANY OTHER CASE OF IRREGULAR FUNCTIONING 4 PERIODIC MAINTENANCE W W W WA A A AR R R RN N N NI I I IN N N NG G G G THIS PROCEDURE MAY ONLY BE DONE BY AN AUTHORISED TECNOMAC INSTALLATION TECHNICIAN STEAM BOILER UNIT Maintenan...

Page 6: ...DS FILL AND DRAIN SOLENOID VALVES Disconnect the power supply leads Remove the fill drain solenoid valve Remove any possible salt deposits under a jet of water Check the conditions of the flow sensor with in the fill solenoid valve don t use com pressed air as to avoid damages to the flow regulator Refit the valves and power the humidifier DRAINAGE AND STEAM CONVEYANCE PIPINGS These pipes may get ...

Reviews: