GB
12
main electrodes;
– Remove the plugs from the high level elec-
trodes;
– Remove the fixing bracket to free the cylin-
der;
– Lift the cylinder and remove it.
Before replacing it:
– Check that the gasket between cylinder and
drain section is in good conditions;
– Replace the cylinder and follow the indication
above, starting from the last point.
IT IS RECOMMENDED TO COMPLETELY
EMPTY THE CYLINDER ANY TIME THE
HUMIDIFIER WILL REMAIN INACTIVE FOR
LONG PERIODS.
FILL AND DRAIN SOLENOID VALVES
– Disconnect the power supply leads;
– Remove the fill/drain solenoid valve;
– Remove any possible salt deposits under a
jet of water;
– Check the conditions of the flow sensor with-
in the fill solenoid valve: don’t use com-
pressed air as to avoid damages to the flow
regulator;
– Refit the valves and power the humidifier.
DRAINAGE AND STEAM
CONVEYANCE PIPINGS
These pipes may get damaged because of the
high temperatures they undergo during normal
function of the humidifier. Please check period-
ically their conditions and - if necessary -
replace them.
NOTE: ALL THE MAINTENANCE HAS TO BE
DONE AFTER DISCONNECTING THE HUMIDI-
FIER.