Tecnologic TLK 94 Operating Instructions Manual Download Page 5

Programming par. “rot”=1,000, in par. “OFSt” it is possible to set a
positive or negative offset that is simply added to the value read by

the probe before visualisation, which remains constant for all the
measurements.

If instead, it is desired that the offset set should not be constant for
all the measurements, it is possible to operate the calibration on  

any two points. 
In this case, in order to decide which values to program on par.

“OFSt” and “rot”, the following formulae must be applied :

“rot” = (D2-D1) / (M2-M1) “OFSt” = D2 - (“rot” x M2)

where:

M1 =measured value 1
D1 = visualisation value when the instrument measures M1

M2 =measured value 2
D2 = visualisation value when the instrument measures M2

It then follows that the instrument will visualise :

DV = MV x “rot” +  “OFSt”

where:  DV = visualised value 

MV= measured value

Example 1: It is desired that the instrument visualises the value
effectively measured at 20° but that, at 200°, it visualises a value

lower than 10° (190°).    
Therefore :  M1=20 ;  D1=20 ;  M2=200 ;  D2=190

“rot” = (190 - 20) / (200 - 20) = 0,944
“OFSt” = 190 - (0,944 x 200) = 1,2
Example 2: It is desired that the instrument visualises 10° whilst the

value actually measured is 0°, but, at 500° it visualises a 50° higher
value (550°).

Therefore :  M1=0 ;  D1=10 ;  M2=500 ;  D2=550
“rot” = (550 - 10) / (500 - 0) = 1,08
“OFSt” = 550 - (1,08 x 500) = 10
By using par.

 “FiL” 

it is possible to

 

program time constant of the  

software filter for the input value measured, in order to reduce
noise sensitivity (increasing the time of reading).

In case of measurement error, the instrument supplies the power
as programmed on par.  

“OPE”.

This power will be calculated according to cycle time programmed

for the PID controller, while for the ON/OFF controllers the cycle
time is automatically considered to be equal to 20 sec. (e.g. In the

event of probe error with ON/OFF control and “OPE”=50, the
control output will be activated for 10 sec., then it will be

deactivated for 10 sec. and so on until the measurement error
remains.).
By using par. 

“InE”

 it is also possible to decide the conditions of

the input error, allowing the instrument to give the power  
programmed on par. “OPE” as output.

The possibilities of par. “InE” are :
= Or : the condition occurs in case of over-range or probe breakage

= Ur : the condition occurs in case of under-range or probe
breakage

= OUr : the condition occurs in case of over-range or under-range
or probe breakage
Using par. 

“diSP”, 

located in the group 

]

PAn”, 

it is possible to set

normal visualization of the SV display which can be the active Set
Point (SP.F), the control power (Pou), the Set Point operating when
there are active ramps (SP.o) or alarm threshold AL1, 2, 3, 4 .

4.2 - OUTPUT CONFIGURATION

The instrument’s outputs can be programmed by entering the
group of parameters 

]

Out” 

where different parameters (depending

on the type of outputs - digital or analogue - available on the
instrument) are located.

Note:

 In the following examples, the number of outputs is

generically indicated  with 

n

- DIGITAL OUTPUTS relay or  SSR type :

The par. 

“OnF”

 can be set for the following functions :

= 1.rEG : Main control output
= 2.rEG : Secondary control output

= ALno : Alarm output normally open
= ALnc : Alarm output normally closed

= On : Output always activated
= OFF : Output deactivated 

The coupling outputs number outputs – number alarms can be
made in the group referring to the alarm to the alarm (“

]

AL1, 2, 3,

4”). The option "On" it results usable for the output OUT6 (standard
on all the models) to have an auxiliary supply output for input

sensors

- ANALOGICAL OUTPUTS 0/4..20 mA or 0/2..10 V (only
OUT1,2):

With the parameter 

“Aorn”

 it is possible to set the beginning of the

scale used for the output.

This parameter will therefore be set at:
= 0 : if one intends to use the beginning of the scale as equal to 0

(0 mA if the output is 0/4...20  mA, or 0 V if the output is  0/2...10 V)
= no_0 : if one intends to use the beginning of the scale other than

0  (4 mA if the output is 0/4...20 mA, or 2 V if the output is 0/2...10
V)
The parameter 

“AonF”

 will be present by which it is possible to

configure the function of the analogical output as:

= 1.rEG : Primary control output 
= 2.rEG : Secondary control output

= r.inP : measurement retransmission output
= r.Err : error retransmission output [SP-PV]

= r.SP : Active Set Point retransmission output
= r.SEr : output led by serial communication line of the instrument

= OFF : deactivated output
In the case that analogical output is configured as 1.rEG or 2.rEG

the output signal  will be proportional to the control power
calculated by the instrument starting from 0% (output signal

corresponding to the set beginning of the scale) up to 100% (output
signal corresponds to the maximum that can be supplied by the

type of output available).
The analogical control outputs can only be used for PID single

action or dual action controls.
If the set control mode was the ON/OFF type, the analogical output

could only take on the control states 0 % or 100 %.
In the case that the analogical output function should be configured

for the retransmission of the signal, it is therefore necessary to
programme another two parameters which set the minimum and

maximum reference values.
Therefore, in these cases, set the parameter 

"AonL"

 with the value

that the instrument must provide the minimum value (0/4 mA or 0/2

V) in output and the value to which the instrument must provide the
maximum value (20 mA o 10 V) to the parameter

 "AonH"

 in output.

4.3 - ON/OFF CONTROL  (1.rEG)

All the parameters referring to the ON/OFF control are contained in
the group 

]

rEG”.

This type of control can be obtained by programming par.

"Cont"

 =

On.FS or = On.FA  and works on the output programmed as 

1.rEG,

depending on the measure, on the active Set Point 

“SP”

, on the

functioning mode 

"Func” 

and on the hysteresis 

"HSEt

".

The instrument carries out an ON/OFF control with symmetric

hysteresis if “Cont" = On.FS or with asymmetrical hysteresis if
“Cont” = On.FA.

O UT

S P

PV

o ff

O N

H EAt - O n.F A

O UT

tim e

H S Et

S P

P V

H SE t

tim e

C ooL -  O n.F A

O N

O N

O N

O N

O N

off

off

o ff

C ooL -  O n.FS

H EAt - O n.F S

O N

O N

O UT

S P

o ff

PV

off

O N

H S Et

tim e

O UT

O N

S P

P V

O N

off

o ff

O N

tim e

H SE t

H S Et

H SE t

1.rE G

1.rEG

1.rEG

1.rE G

The control works in the following way : in the case of reverse
action, or heating (“FunC”=HEAt), it deactivates the output, when

the process value reaches [SP + HSEt] in case of symmetrical
hysteresis, or [SP] in case of asymmetrical hysteresis and is then

activated again when the process value goes below value [SP -
HSEt]. Vice versa, in case of direct action or cooling

("Func”=CooL), it deactivates the output, when the process value

TECNOLOGIC spa - TLK 94

 

-OPERATING INSTRUCTIONS - Vr.01 - 01/10 - ISTR-MTLK94ENG1 - PAG. 5

Summary of Contents for TLK 94

Page 1: ...ONS 4 14 SOFT START FUNCTION 4 13 REACHING OF SET POINT AT CONTROLLED SPEED AND AUTOMATIC COMMUTATION BETWEEN TWO SET POINTS 4 12 SPLIT RANGE FUNCTION 4 11 LIMITATION OF THE CONTROL POWER VARIATION SPEED MAXIMUM RATE OF RISE 4 10 CONTROL POWER LIMITATION 4 9 AUTO TUNING AND SELF TUNING FUNCTIONS 4 8 PID CONTROL FOR MOTORIZED ACTUATORS WITH TIME POSITIONING 4 7 DOUBLE ACTION PID CONTROL 4 6 SINGLE ...

Page 2: ...s access to the programming mode and the parameters level see par 2 3 12 Led TUN indicates that the Self tuning function is activated light on or that Auto tuning flashing is in progress 13 Display PV normally indicates the process value 14 Display SV normally indicates the active Set value however it can be programmed using par diSP to visualize other values 2 PROGRAMMING 2 1 FAST PROGRAMMING OF ...

Page 3: ...ained in the group PAn This parameter can be programmed as SE The active Set Point can be modified while the alarm thresholds cannot be modified AE The active Set Point cannot be modified while the alarm thresholds can be modified SAE Both the active Set Point and the alarm thresholds can be modified SAnE Both the active Set Point and the alarm thresholds cannot be modified 2 4 CONTROL STATE The c...

Page 4: ... probe has to be kept separate from line voltage wiring If the input cable of the probe is screened it has to be connected to the ground with only one side We recommend that a check should be made that the parameters are those desired and that the application functions correctly before connecting the outputs to the actuators so as to avoid malfunctioning that may cause irregularities in the plant ...

Page 5: ...ivated The coupling outputs number outputs number alarms can be made in the group referring to the alarm to the alarm AL1 2 3 4 The option On it results usable for the output OUT6 standard on all the models to have an auxiliary supply output for input sensors ANALOGICAL OUTPUTS 0 4 20 mA or 0 2 10 V only OUT1 2 With the parameter Aorn it is possible to set the beginning of the scale used for the o...

Page 6: ...ble overshoots at the start up of the process or at the changing of the Set Point to be avoided Please remember that a low value on this parameter reduces the overshoot while a high value increase it 2 1 3 S P P V tim e 1 FuOC OK 2 FuOC too high 3 FuOC too low 4 6 DOUBLE ACTION PID CONTROLLER 1 rEG 2 rEG All the parameters referred to PID control are contained into the group rEG The Double Action ...

Page 7: ...ed on on the condition that the process value is lower with Func HEAt than SP SP 2 or higher with Func CooL than SP SP 2 2 if FAST autotuning is desired automatically the next time the instrument is switched on on the condition that the process value is lower with Func HEAt than SP SP 2 or higher with Func CooL than SP SP 2 and once the tuning is finished the par Auto is automatically swapped to t...

Page 8: ... output from 1 rEG H ro2 L minimum power in output from 2 rEG C ro2 H maximum power in output from 2 rEG C The limitation is not active under the OPLO manual control mode 4 10 LIMITATION OF THE CONTROL POWER VARIATION SPEED This function makes it possible to limit the variation speed of the control power in output separately for both control outputs It is only possible to use this function if the ...

Page 9: ... HSEt End Soft Start cycle threshold If both parameters are programmed with values other than OFF when switched on the instrument gives an output power as programmed on par St P for the time programmed on par SSt or when is reached the absolute value programmed at par HSEt Practically the instrument works in manual condition and switches to automatic control at the elapsing of time SSt or when is ...

Page 10: ...AL1d expressed in sec and the alarm will be activated only after the elapsing of that time ALARM LATCH the alarm output may behave in two different ways depending on the value added to par Ab1 0 ALARM NOT LATCHED The alarm remains active in alarm conditions only 4 ALARM LATCHED The alarm is active in alarm conditions and remains active even when these conditions no longer exist until the correctly...

Page 11: ...vention the instrument visualizes the message LbA and behaves as in the case of a measurement error giving a power output as programmed on par OPE programmable in the group InP To restore normal functioning after the alarm select the control mode OFF and then re program the automatic control rEG after checking the correct functioning of probe and drive To exclude the Loop Break alarm set OLbA OFF ...

Page 12: ...programming of the instruments which need to have the same parameters configuration or to keep a copy of the programming of an instrument and allow its rapid retransmission To use the device A01 it s necessary that the device or instrument are being supplied Instrument supplied and device not supplied SUPPLY Instrument supplied from the device ADAPTER SUPPLY AC SUPPLY 12 VDC P A For the instrument...

Page 13: ...ut on OFF Output off O1F 22 Note Def Range Description Par On 1 rEG 2 rEG ALno ALnc On OFF Functioning of output 6 see O1F O6F 35 OFF 1 rEG 2 rEG ALno ALnc On OFF Functioning of output 5 see O1F O5F 34 OFF 1 rEG 2 rEG ALno ALnc On OFF Functioning of output 4 see O1F O4F 33 OFF 1 rEG 2 rEG ALno ALnc On OFF Functioning of output 3 see O1F O3F 32 0 Ao2L 9999 Maximum reference for analogical output 2 ...

Page 14: ... OLbA 72 Note Def Range Description Par Group Hb parameters relative to Heater Break Alarm OFF Out1 Out2 Out3 Out4 Output where alarm HB is addressed OHb 74 Note Def Range Description Par 100 0 IHbL IFS High alarm HB threshold with Out 1 rEG OFF IHbH 78 0 0 0 0 IFS Low alarm HB threshold with Out 1 rEG ON IHbL 77 1 1 2 3 4 HB Alarm function 1 Min 1 rEG on 2 Max 1 rEG off 3 Min 1 rEG on and Max 1 r...

Page 15: ... Once the error has been found try to repeat the auto tuning FAST Autotuning not possible because the process value is too higher or too lower ErAt The measured variable is over the probe s limits over range oooo The measured variable is under the probe s limits under range uuuu Verify the correct connection between probe and instrument and then verify the correct functioning of the probe Probe in...

Page 16: ...n PID PID for motorized actuators with time positioning Measurement range according to the used probe see range table Display resolution according to the probe used 1 0 1 0 01 0 001 Overall accuracy 0 2 fs 1 digit PTC NTC 0 5 fs 1 digit Max cold junction compensation drift in tc 0 04 C C with operating temperature 0 50 C after warm up of 20 min Sampling rate 130 ms Serial Interface RS485 insulated...

Page 17: ... PTC KTY81 121 HCFG rtd SEnS Ptc 199 9 850 0 C 199 9 999 9 F 200 850 C 328 1562 F Pt100 IEC HCFG rtd SEnS Pt1 7 6 INSTRUMENT ORDERING CODE TLK94 a b c d e f g h i j kk ll m a POWER SUPPLY L 24 VAC VDC H 100 240 VAC b OUTPUT OUT1 R OUT1 Relay O OUT1 VDC for SSR I OUT1 analog 0 4 20 mA V OUT1 analog 0 2 10 V c OUTPUT OUT2 R OUT2 Relay O OUT2 VDC for SSR I OUT1 analog 0 4 20 mA V OUT1 analog 0 2 10 V...

Reviews: