Tecnologic TLK 94 Operating Instructions Manual Download Page 11

= ALno

 if the alarm output has to be active when the alarm is

active while it is deactivated when the alarm is not active.

= ALnc

 if the alarm output has to be active when the alarm is not

active while it is deactivated when the alarm is active. 
Enter group 

]

Hb”

 and program which output the alarm signal has

to address on parameter 

“OHb

The functioning mode of the alarm is instead defined on par.

“HbF”

 which can be set in the following way :

= 1

 : The alarm is active when, with output 1rEG active, the current

measured by the input TAHB is lower than the value programmed
on par. 

"IHbL"

 .

= 2

 : The alarm is active when, with output 1rEG not active, the cur-

rent measured by the input TAHB is higher than the value pro-
grammed on par. 

"IHbH"

 .

= 3

 : The alarm is active when, with output 1rEG active, the current

measured by the input TAHB is lower than the value programmed
on par. 

"IHbL"

 or with output 1rEG not active, the current meas-

ured by the input TAHB is higher than the value programmed on
par. 

"IHbH"

.

= 4

 : The alarm is active when the current measured by the input

TAHB is lower than the value programmed on par. 

"IHbL" 

or the

measured current is higher than the value programmed on par.

"IHbH"

, independently by the state of the output 1.rEG.   

On par. “IHbL” the value of the current normally absorbed by the
load when output 1.rEG is active has to be set, while on par. “IHbH”

the current normally absorbed by the load when output 1.rEG is not
active.

The programming of these parameters has to be carried out while
also considering the fluctuations of the net voltage to avoid

undesired alarms.
With regards to the hysteresis of the HB alarm, this is automatically

calculated by the instrument as 1% of the programmed thresholds.
During functioning it is possible to visualize the current measured

by the input TAHB when output 1rEG is activated, by pushing the
“DOWN” key and the current measured when output 1.rEG is deac-

tivated, by pushing the “DOWN” and “U” keys at the same time.
To exclude the Heater Break alarm it is enough to set “OHb” =
OFF.

Note :

 The HB current measurement is valid if the output 1rEG is

activated (or deactivated) for 264 ms. at least. 
This means that, if the cycle time (“tcr1”) is = 1 sec, the HB alarm is
able to intervene only when the output power is higher than 26,4%.

4.16 - LOOP BREAK ALARM FUNCTION

All the parameters referring to the Loop Break alarm function are
contained in the group 

]

LbA”.

The Loop Break alarm is available on all the instruments, which
intervenes when, for any reason (short-circuit of a thermocouple,

thermocouple inversion, load interruption), the loop control is
interrupted.

First of all, it is necessary to establish to which output the alarm
has to correspond.  

To do this it is necessary to set the parameter relative to the output
to be used (“O1F”, “O2F”, “O3F”, “O4F”, “O5F”, “O6F”) in the
groups 

]

Out ”, 

programming the parameter as :

= ALno

 if the alarm output has to be ON when the alarm is active

while it is OFF when the alarm is not active.

= ALnc

 if the alarm output has to be ON when the alarm is not

active while it is OFF when the alarm is active. 
Enter group  

]

LbA”

 and program which output the alarm signal

has to be addressed to on par. 

“OLbA”

The Loop Break alarm is activated if the output power remains at
the 100% of the value for the time programmed on par. 

"LbAt"

(expressed in sec.).

To avoid false alarms, the value of this parameter has to be set
considering the time the plant takes to reach the Set point when

the measured value is a long distance from it (for example at the
plant start-up). 

On alarm intervention, the instrument visualizes the message

“LbA”

 and behaves as in the case of a measurement error giving a

power output as programmed on par.  

“OPE”

 (programmable in

the group 

]

InP”)

.

To restore normal functioning after the alarm, select the control
mode “OFF” and then re-program the automatic control (“rEG”)

after checking the correct functioning of probe and drive.
To exclude the Loop Break alarm, set “OLbA” = OFF.

4.17 - FUNCTIONING OF KEY “U”

The function of key “U” can be set through par. 

“USrb”

 contained

in the group “

]

PAn”.

The parameter can be programmed as :

= noF

 : no function

= tunE

 : Pushing the key for 1 sec. at least, it is possible to

activate/deactivate Auto-tuning or Self-tuning

= OPLO

 : Pushing the key for 1 sec. at least, it is possible to swap

from automatic control  (rEG) to manual one (OPLO) and vice

versa.

= Aac

 : Pushing the key for 1 sec. at least, it is possible to

acknowledge the alarm. (see par. 4.14)

= ASi 

: Pushing the key for 1 sec. at least, it is possible to

acknowledge an active alarm (see par. 4.14)
 

= CHSP

 : Pushing the key for 1 sec. at least, it is possible to select

one of the 4 pre-programmed Set Points on rotation. 

= OFF

 : Pushing the key for 1 sec. at least, it is possible to swap

from automatic control  (rEG) to OFF control (OFF) and vice versa.

4.18 - DIGITAL INPUT

The instrument is equipped with 2 digital inputs whose function can
be set by the parameter 

"diF"

 contained in the group 

]

InP”.

The parameter can be programmed as:

= noF

 : the input does not carry out any function

= AaC

 : By closing the contact connected to the digital input, it is

possible to reset a memorised alarm (see par. 4.14)

= ASi: 

By closing the contact connected to the digital input, it is

possible to silence an active alarm (see par. 4.14)

=

 

HoLd

: By closing the contact connected to the digital input the

measurement taken at that moment is blocked (N.B.: not the
reading on the display, therefore the indication may stabilise itself

with a delay that is proportional to the measuring filter). With the
hold function turned on, the instrument carries out control

according to the memorised measurement. By opening the contact,
the instrument starts normal measurement acquisition once more.

= OFF

 : When the instrument is in “rEG” status, by closing the

contact connected to the digital input, the instrument is placed in
OFF status. By reopening the contact, the instrument returns to the

automatic control status  “rEG”.

= CHSP

 : by closing and reopening the contact connected to the

digital input, it is possible to select one of the 4 memorised set

points in rotation. 

= SP1.4 

: The following combination of the connected contacts to

the two digital entries allows the activation of one of the 4

memorized set points. 

SP4

on

on

SP3

on

off

SP2

off

on

SP1

off

off

SET POINT

DIG IN2

DIG IN1

The function can be activated using “nSP” = 4 , also, when it is acti-
vated, it disables the selection of the active set by the parameter

“SPAt” and by the key U.

= HE.Co 

: by closing the contact connected to the digital input it is

possible to select as active the set point SP2 in “CooL” mode. Reo-

pening the contact is select as active the set point SP1 in “HEAt”
mode. This function is possible only when “nSP” = 2.

4.19 - RS 485 SERIAL INTERFACE

The instrument can be equipped with a RS 485 serial

communication interface, by means of which it is possible to
connect the regulator with a net to which other instruments

(regulators of PLC) are connected, all depending typically on a
personal computer used as plant supervisor. Using a personal

computer it is possible to acquire all the function information and to
program all the instrument’s configuration parameters. The

software protocol adopted for TLK94 is a MODBUS RTU type,

TECNOLOGIC spa - TLK 94

 

-OPERATING INSTRUCTIONS - Vr.01 - 01/10 - ISTR-MTLK94ENG1 - PAG. 11

Summary of Contents for TLK 94

Page 1: ...ONS 4 14 SOFT START FUNCTION 4 13 REACHING OF SET POINT AT CONTROLLED SPEED AND AUTOMATIC COMMUTATION BETWEEN TWO SET POINTS 4 12 SPLIT RANGE FUNCTION 4 11 LIMITATION OF THE CONTROL POWER VARIATION SPEED MAXIMUM RATE OF RISE 4 10 CONTROL POWER LIMITATION 4 9 AUTO TUNING AND SELF TUNING FUNCTIONS 4 8 PID CONTROL FOR MOTORIZED ACTUATORS WITH TIME POSITIONING 4 7 DOUBLE ACTION PID CONTROL 4 6 SINGLE ...

Page 2: ...s access to the programming mode and the parameters level see par 2 3 12 Led TUN indicates that the Self tuning function is activated light on or that Auto tuning flashing is in progress 13 Display PV normally indicates the process value 14 Display SV normally indicates the active Set value however it can be programmed using par diSP to visualize other values 2 PROGRAMMING 2 1 FAST PROGRAMMING OF ...

Page 3: ...ained in the group PAn This parameter can be programmed as SE The active Set Point can be modified while the alarm thresholds cannot be modified AE The active Set Point cannot be modified while the alarm thresholds can be modified SAE Both the active Set Point and the alarm thresholds can be modified SAnE Both the active Set Point and the alarm thresholds cannot be modified 2 4 CONTROL STATE The c...

Page 4: ... probe has to be kept separate from line voltage wiring If the input cable of the probe is screened it has to be connected to the ground with only one side We recommend that a check should be made that the parameters are those desired and that the application functions correctly before connecting the outputs to the actuators so as to avoid malfunctioning that may cause irregularities in the plant ...

Page 5: ...ivated The coupling outputs number outputs number alarms can be made in the group referring to the alarm to the alarm AL1 2 3 4 The option On it results usable for the output OUT6 standard on all the models to have an auxiliary supply output for input sensors ANALOGICAL OUTPUTS 0 4 20 mA or 0 2 10 V only OUT1 2 With the parameter Aorn it is possible to set the beginning of the scale used for the o...

Page 6: ...ble overshoots at the start up of the process or at the changing of the Set Point to be avoided Please remember that a low value on this parameter reduces the overshoot while a high value increase it 2 1 3 S P P V tim e 1 FuOC OK 2 FuOC too high 3 FuOC too low 4 6 DOUBLE ACTION PID CONTROLLER 1 rEG 2 rEG All the parameters referred to PID control are contained into the group rEG The Double Action ...

Page 7: ...ed on on the condition that the process value is lower with Func HEAt than SP SP 2 or higher with Func CooL than SP SP 2 2 if FAST autotuning is desired automatically the next time the instrument is switched on on the condition that the process value is lower with Func HEAt than SP SP 2 or higher with Func CooL than SP SP 2 and once the tuning is finished the par Auto is automatically swapped to t...

Page 8: ... output from 1 rEG H ro2 L minimum power in output from 2 rEG C ro2 H maximum power in output from 2 rEG C The limitation is not active under the OPLO manual control mode 4 10 LIMITATION OF THE CONTROL POWER VARIATION SPEED This function makes it possible to limit the variation speed of the control power in output separately for both control outputs It is only possible to use this function if the ...

Page 9: ... HSEt End Soft Start cycle threshold If both parameters are programmed with values other than OFF when switched on the instrument gives an output power as programmed on par St P for the time programmed on par SSt or when is reached the absolute value programmed at par HSEt Practically the instrument works in manual condition and switches to automatic control at the elapsing of time SSt or when is ...

Page 10: ...AL1d expressed in sec and the alarm will be activated only after the elapsing of that time ALARM LATCH the alarm output may behave in two different ways depending on the value added to par Ab1 0 ALARM NOT LATCHED The alarm remains active in alarm conditions only 4 ALARM LATCHED The alarm is active in alarm conditions and remains active even when these conditions no longer exist until the correctly...

Page 11: ...vention the instrument visualizes the message LbA and behaves as in the case of a measurement error giving a power output as programmed on par OPE programmable in the group InP To restore normal functioning after the alarm select the control mode OFF and then re program the automatic control rEG after checking the correct functioning of probe and drive To exclude the Loop Break alarm set OLbA OFF ...

Page 12: ...programming of the instruments which need to have the same parameters configuration or to keep a copy of the programming of an instrument and allow its rapid retransmission To use the device A01 it s necessary that the device or instrument are being supplied Instrument supplied and device not supplied SUPPLY Instrument supplied from the device ADAPTER SUPPLY AC SUPPLY 12 VDC P A For the instrument...

Page 13: ...ut on OFF Output off O1F 22 Note Def Range Description Par On 1 rEG 2 rEG ALno ALnc On OFF Functioning of output 6 see O1F O6F 35 OFF 1 rEG 2 rEG ALno ALnc On OFF Functioning of output 5 see O1F O5F 34 OFF 1 rEG 2 rEG ALno ALnc On OFF Functioning of output 4 see O1F O4F 33 OFF 1 rEG 2 rEG ALno ALnc On OFF Functioning of output 3 see O1F O3F 32 0 Ao2L 9999 Maximum reference for analogical output 2 ...

Page 14: ... OLbA 72 Note Def Range Description Par Group Hb parameters relative to Heater Break Alarm OFF Out1 Out2 Out3 Out4 Output where alarm HB is addressed OHb 74 Note Def Range Description Par 100 0 IHbL IFS High alarm HB threshold with Out 1 rEG OFF IHbH 78 0 0 0 0 IFS Low alarm HB threshold with Out 1 rEG ON IHbL 77 1 1 2 3 4 HB Alarm function 1 Min 1 rEG on 2 Max 1 rEG off 3 Min 1 rEG on and Max 1 r...

Page 15: ... Once the error has been found try to repeat the auto tuning FAST Autotuning not possible because the process value is too higher or too lower ErAt The measured variable is over the probe s limits over range oooo The measured variable is under the probe s limits under range uuuu Verify the correct connection between probe and instrument and then verify the correct functioning of the probe Probe in...

Page 16: ...n PID PID for motorized actuators with time positioning Measurement range according to the used probe see range table Display resolution according to the probe used 1 0 1 0 01 0 001 Overall accuracy 0 2 fs 1 digit PTC NTC 0 5 fs 1 digit Max cold junction compensation drift in tc 0 04 C C with operating temperature 0 50 C after warm up of 20 min Sampling rate 130 ms Serial Interface RS485 insulated...

Page 17: ... PTC KTY81 121 HCFG rtd SEnS Ptc 199 9 850 0 C 199 9 999 9 F 200 850 C 328 1562 F Pt100 IEC HCFG rtd SEnS Pt1 7 6 INSTRUMENT ORDERING CODE TLK94 a b c d e f g h i j kk ll m a POWER SUPPLY L 24 VAC VDC H 100 240 VAC b OUTPUT OUT1 R OUT1 Relay O OUT1 VDC for SSR I OUT1 analog 0 4 20 mA V OUT1 analog 0 2 10 V c OUTPUT OUT2 R OUT2 Relay O OUT2 VDC for SSR I OUT1 analog 0 4 20 mA V OUT1 analog 0 2 10 V...

Reviews: