MENU 05 – ENGINE CONTROL
Default
Range
P0501 Alarms inhibition at starting (sec)
8
1-120
P0502 Time of inhibition for frequency alarm during starting
OFF
OFF/ 0..300
P0503 MAX “W” speed limit (%)
110
100-120
P0504 MAX “W” speed delay (s)
3
0.5-60.0
P0505 MIN ”W” speed limit (%)
90
80-100
P0506 MIN “W” speed delay (sec)
5
0-600
MENU 06 – MAINS CONTROL
Default
Range
P0601 MIN voltage limit (%)
85
70-100
P0602 MIN voltage delay (sec)
5
0-600
P0603 MAX voltage limit (%)
115
100-130 / OFF
P0604 MAX voltage delay (sec)
5
0-600
P0605 Mains into limits delay (sec)
20
1-9999
P0606 MIN/MAX hysteresis limit (%)
3.0
0.0-5.0
P0607 MAX asymmetry limit (%)
15
OFF / 5-25
P0608 MAX asymmetry delay (sec)
5
0-600
P0609 MAX frequency limit (%)
110
100-120/OFF
P0610 MIN frequency limit (%)
90
OFF/80-100
P0611 MIN/MAX frequency delay (sec)
5
0-600
P0612 Mains control OFF/internal/external
INT
OFF / INT / Out
P0613 Mains control in RESET/OFF mode
OFF
OFF/ON/OFF+GLOB/ON+GLOB
P0614 Mains control in MAN mode
OFF
OFF/ON/OFF+GLOB/ON+GLOB
P0615 Time of delay for generating starting
OFF
OFF / 1-9999
P0616 Delay mains return on limits if genset is off (s)
2
0-9999
MENU 07 – GEN CONTROL
Default
Range
P0701 MIN voltage limit (%)
80
70 -100
P0702 MIN voltage delay (sec)
5
0-6000
P0703 MAX voltage limit (%)
115
100-130 / OFF
P0704 MAX voltage delay (sec)
5
0-6000
P0705 Generator into limits delay (sec)
20
0-9999
P0706 MIN/MAX hysteresys limit (%)
3.0
0.0-5.0
P0707 MAX asymmetry limit (%)
15
5-20
P0708 MAX asymmetry delay (sec)
5
0-600
P0709 MAX frequency limit (%)
110
100-120/OFF
P0710 MAX frequency delay (sec)
3
0-200
P0711 MIN frequency limit (%)
90
OFF/80-100
P0712 MIN frequency delay (sec)
5
0-600
P0713 Gen control (OFF/internal/external)
INT
OFF/INT/Out
P0714 generator voltage alarms delay
240
1-600
MENU 08 – GENERATOR PROTECTION
Default
Range
P0801 Rated generator current (A)
OFF
OFF/5-10000
P0802 MAX current limit (%)
OFF
100-500/OFF
P0803 Immediate Intervention current limit (%)
OFF
100-500/OFF
P0804 MAX current delay (sec)
40
0-600
P0805 Generator protection reset time (sec)
60
0-5000
MENU 09 – TEST AND MAINTENANCE
Default
Range
P0901 Automatic test on
OFF
OFF / ON
P0902 interval between TESTS (days)
7
1-30
P0903 To enable carrying out on Monday
ON
OFF / ON
P0904 To enable carrying out on Tuesday
ON
OFF / ON
P0905 To enable carrying out on Wednesday
ON
OFF / ON
P0906 To enable carrying out on Thursday
ON
OFF / ON
P0907 To enable carrying out on Friday
ON
OFF / ON
P0908 To enable carrying out on Saturday
ON
OFF / ON
P0909 To enable carrying out on Sunday
ON
OFF / ON
P0910 test beginning hour (h)
12
00-23
P0911 test beginning minutes (min)
00
00-59
P0912 automatic test duration (min)
OFF
OFF/1-600
P0913 Automatic test with load switching
OFF
OFF / G.con / du.Lo
P0914 automatic test with external stop
OFF
OFF/ON
P0915 Maintenance interval (h)
OFF
OFF/1-9999
P0916 TEST way with switching load
OFF
OFF / G.con / du.Lo