1) Push RESET + MEAS for 5 seconds at the same time. You can release buttons when first parameter “01.01” is shown on the display. To change
menu/parameters, push MEAS up to reach parameter
“09.01”
, that is the first parameter of menu number 9, called “TEST AND
MAINTENANCE”. The above table shows all the adjustable parameters in this menu. In this case, parameter “09.01” allows to activate or to
disable the automatic test.
2) Push TEST or MAN to look at the setting. If you go on pushing TEST or MAN, you can modify to ON (activated test) or to OFF (disabled test).
When the automatic test is on, the yellow led on TEST
button is switched on. When the automatic test is disables, the yellow led on TEST
button is switched off. If you don’t push any buttons, the board display comes back showing parameter “
09.01
” after 2 seconds.
3) Push TEST
button to move to the next parameter “
09.02
”; if you want to come back to previous parameters press STOP button. This
parameter allows to set the waiting days between an automatic test and the next one. Push TEST or MAN to look at the setting; if you go on
pushing TEST you can increase the value, if you go on pushing MAN you can decrease the value. If you don’t push any buttons, the board
display comes back showing parameter “
09.02
” after 2 seconds.
4) Push TEST
button to move to next parameter “
09.03
”; this parameter allows to set activated automatic test on Monday. Push TEST or MAN to
look at the setting; if you go on pushing TEST or MAN, you can modify to ON (activated test) or to OFF (disabled test) the test on this day. If you
don’t push any buttons, the board display comes back showing parameter “
09.03
” after 2 seconds.
5) Follow the above procedure until parameter “
09.09
” regarding test on Sunday. Then, press TEST
button to move to next parameter “
09.10
”,
regarding automatic test starting hour. Push TEST or MAN to look at the setting; if you go on pushing TEST you can increase the value, if you go
on pushing MAN you can decrease the value. If you don’t push any buttons, the board display comes back showing parameter “
09.10
” after 2
seconds.
6) Push TEST
button to move to next parameter “
09.11
”; this parameter allows to set the starting minute of automatic test. Push TEST or MAN to
look at the setting; if you go on pushing TEST you can increase the value, if you go on pushing MAN you can decrease the value. If you don’t
push any buttons, the board display comes back showing parameter “
09.11
” after 2 seconds.
7) Push TEST
button to change to next parameter “
09.12
”; this parameter allows to set the automatic test duration. Push TEST or MAN to look at
the setting; if you go on pushing TEST you can increase the value, if you go on pushing MAN you can decrease the value. If you don’t push any
buttons, the board display comes back showing parameter “
09.12
”.
The automatic test programming is now finished. If you want to review or change previous parameters, press STOP button and follow the above
described procedure. Press RESET button to save the statements and exit the menu to come back to normal operating mode.
You can activate automatic test (as parameter “
09.01
”) directly from normal operating mode: push TEST
+ START (yellow TEST
led turns ON)
at the same time.
You can disable automatic test (as parameter “
09.01
”) directly from normal operating mode: TEST
+ STOP (yellow TEST
led turns OFF) at the
same time.
The parameter 09.13 set the automatic test with switching load (G.con) or dummy load (du.Lo). By default is programmed without both switching.
The parameter 09.14 permts to enable the automatic test also if the remote start signal is closed on terminal 8.6 (by default is programmed to
disable the test if the remote stop signal is closed).
EXAMPLE:
MENU 09 – TEST AND MAINTENANCE
Default
Range
09.01 Automatic test on
ON
OFF / ON
09.02 Interval between TESTS (days)
3
1-30
09.03 To enable test on Monday
ON
OFF / ON
09.04 To enable test on Tuesday
OFF
OFF / ON
09.05 To enable test on Wednesday
OFF
OFF / ON
09.06 To enable test on Thursday
OFF
OFF / ON
09.07 To enable test on Friday
ON
OFF / ON
09.08 To enable test on Saturday
OFF
OFF / ON
09.09 To enable test on Sunday
OFF
OFF / ON
09.10 Hour starting test (h)
10
00-23
09.11 Minutes starting test (min)
15
00-59
09.12 Automatic test duration (min)
10
OFF/1-600
By using as example the above table, the automatic test functioning is the following:
- Today, Tuesday, the automatic test function is activated; 3 days later (next Friday), the automatic test runs.
- In parameter
09.07
Friday is activated; by this the test runs at 10:15 (
09.10
and
09.11
) for 15 minutes (
09.12
), and it finishes at 10:30.
- Next test occurs 3 days later
(09.02)
, on Monday
- In parameter 09.03, also Monday is activated; by this the test runs at 10:15 (
09.10
and
09.11
) for 15 minutes (
09.12
), and it finishes at 10:30.
- Next test occurs 3 days later
(09.02)
, on Thursday; this day is not activated
(09.06)
. Automatically, the test splits on next day available; in this
case the day is Friday
(09.07)
and the test runs from 10:15 to 10:30 like described before.
- From this day, the board restarts to count other 3 days to next test
(09.02)
; next day is Monday.
- By this programming, the cycle continues in this way: the test runs on Monday and on Friday from 10:15 to 10:30