background image

IST-2137.EO01.01/A

 

Istruzione / User’s Manual / Manuel d’utilisation 

Pag.11/11

 

 

 

 

TECNOCONTROL S.r.l. Via Miglioli 47 SEGRATE ( MI ) 

 Tel: 02/26 92 28 90   Fax: 02/21 33 734

 

 

 

 

Fig. 1 –

 

Dimensioni /

 Size / Dimensions 

 

Fig. 2 -

 

Schema di collegamento / Wiring diagram / Schéma 

12-24

V

 

mA

 

1

 

2

 

3

 

4

 

ON

 

OFF

 

SET

 

 

 

ALARM 1 

 

 

ALARM 2 

ALARM 3 

 

 

FAULT

 

Scheda Uscite Relé 

Relays Output Board 

Sortie sur Realis

 

 

TESTmA

 

12÷24Vdc 

Alimentazione 

Power Supply 

Alimentation

 

Centrale rivelazione gas 

Gas Central Unit 

Centrale de détection

 

RL

-

 

+

 

Uscita in 4÷20 mA 

4÷20 mA Output 

Sortie en 4÷20 mA

 

Dip Switch

 

Test Uscita  

Output Test 

Sortie Test 

40÷200mV

 

 

 

 

Fig. 3 -

 Tester di calibrazione 

/ Calibration Tester / Kit de Calibration 

0,3L/min

 

F1 
F2 

Tasti / Key / Touches 

 

 

Alimentazione / Power Supply / Alimentation

 

100

300

400

500

50

0

5

200

Vdc

RL=Resistenza di carico / Load resistor / Resistance de charge

RL

Ohm

Fig.4 -

 

Alimentazione / Resistenza di Carico 4÷20mA 

Power supply / Load resistance diagram 4÷20mA 

Alimentation / Résistance de charge 4÷20mA

 

600

0

10

15

 

20

 

25

28

650

10,8

24

Area di funzionamento 
Allowable oparating region 

350

700

800

 

Summary of Contents for SE137EO

Page 1: ...e Time Temps de réponse T90 20 secondi seconds secondes Ripetibilità Repeatability Répétitivité 1 del segnale signal Precisione Accuracy Precision 2 del segnale in aria signal in air du signal en air Deriva a lungo termine Long time drift Dérive à long terme 2 segnale mese signal per month du signal chaque mois 5 sulla vita operativa over Operating Life sur sa vie Temp umidità di funzionamento Ope...

Page 2: ...ndi il Led giallo si spegne e si accende il Led verde ON che indica il normale funzionamento Dopo questo tempo il sensore è in grado di rilevare il gas ma raggiunge le condizioni di stabilità ottimali dopo circa 15 minuti di funzionamento continuo Funzionamento Normale deve essere acceso il solo Led Verde ON ALLARMI i tre livelli d allarme possono essere impostati con diverse soglie utilizzando i ...

Page 3: ...trochimici per Ossigeno contengono una piccola quantità di acetato di potassio che è corrosivo Normalmente non si verificano perdite dal sensore questo può essere causato solo da un azione mec canica violenta o un uso oltre i limiti di funzionamento Il sensore contiene anche piccolo quantità di piombo ossido di piombo platino argento carbonio e antimonio Nel caso avvenga un contatto del liquido de...

Page 4: ...i circa 136mV ovvero che l uscita in mA diminuisca fino a circa 13 6 mA Poi i valori dopo aver tolto il gas torneranno progressivamente al valore normale in aria Regolazione Fine Uscita in mA Codice Reg Fine F2 F1 F1 F2 questa funzione permette di regolare l uscita in mA di 0 32mA corrispondente a 0 5 O2 ma va utilizzata solo in fase di installazione e se dopo aver fatto la CALIBRAZIONE IN ARIA pu...

Page 5: ...t try to perform the procedure of Calibration in Air as described in the section Test and Calibration Calibration in Air finally try to replace a new Cartridge Sensor If the condition is not change it will be necessary to replace the unit and or send it back to the supplier to repair All LED activate FAULT relays activate and 24mA output signal this happens when the Cartridge Sensor is not working...

Page 6: ...l operation It is advisable to perform this operation every 6 12 months according to the use Note this function is not working if the 1 and or the 2 and or the 3 red Led have already turned on CALIBRATION IN AIR Calibration Code F2 F2 F2 F1 F2 F1 this function allows completely recalibrate the sensor at 20 9 v v in air This procedure when it is launched will automatically until the end Warning to ...

Page 7: ... mais étant fortement oxydant il réagit avec les matériaux combustibles et réduc teurs en facilitant leur combustion déterminant ainsi des risques d incendie et d explosion L Oxygène constitue 20 95 de l air que nous respirons Si la concentration d O2 dans l air descend sous 19 5 l on considère que cette carence est dommageable pour la santé des personnes si cette concentration descend sous 16 ce ...

Page 8: ...entation de plusieurs détecteurs en parallèle il est nécessaire de calculer la chute de tension sur les portions communes des câbles Un câble sans écran est normalement utilisé avec 2 conducteurs pour l alimentation les conducteurs pour les sorties relais Dans le cas ou l on utilise également le signal de sortie en 4 20 mA il convient d utiliser du câbles à écran à 3 conducteurs les conducteurs po...

Page 9: ...r rompre la procédure puis exécutez le contrôle en coupant et en rétablissant l alimentation du détecteur En cas de persistance il sera nécessaire de remplacer et ou renvoyer le détecteur au fournisseur pour réparation Important Durant l opération de étalonnage l appareil portant la sortie S au 0mA L étalonnage doit être exécuté en air propre exclusivement milieu sans la présence de gaz toxiques o...

Page 10: ...ogni rivelatore dall alimentatore a 12Vcc The maximum distance to install each detec tor from the 12Vdc power Supply Distance max d installation d un détecteur sous 12Vcc La max distanza cui può essere installato ogni rivelatore dall alimentatore a 24Vcc The maximum distance to install each detector from the 24Vdc power Supply Distance max d installation d un détecteur sous 24Vcc 0 75 mm2 26 Ω km ...

Page 11: ...ivelazione gas Gas Central Unit Centrale de détection RL Uscita in 4 20 mA 4 20 mA Output Sortie en 4 20 mA Dip Switch Test Uscita Output Test Sortie Test 40 200mV Fig 3 Tester di calibrazione Calibration Tester Kit de Calibration 0 3L min F1 F2 Tasti Key Touches Alimentazione Power Supply Alimentation 100 300 400 500 50 0 5 200 Vdc RL Resistenza di carico Load resistor Resistance de charge RL Ohm...

Reviews: