Merlin Gas Detectors
Product Data Sheet
Rev: 09 Date: 19-01-18
1
Gas Safety Products
Installation, operating and maintenance
Read these instructions carefully before operating or servicing
Page 1: ...lin Gas Detectors Product Data Sheet Rev 09 Date 19 01 18 1 Gas Safety Products Merlin Gas Detectors Installation operating and maintenance Read these instructions carefully before operating or servic...
Page 2: ...onditions We do recommend that this product is serviced annually If the unit is found to be damaged Contact us Carbon Monoxide CO This apparatus is designed to protect individuals from the acute effec...
Page 3: ...pplied to the panel and should be connected to the terminals marked 2 3 Alarm Relay The Merlin range of gas detectors can work with various systems If you are using the GDP range you will need to use...
Page 4: ...pre alarm Methane 8 LEL by volume LPG 0 16 by volume Carbon monoxide 30ppm Hydrogen 8 LEL by volume High level alarm Methane 10 LEL by volume LPG 0 2 by volume Hydrogen 10 LEL by volume Carbon monoxi...
Page 5: ...er supply negative connection from Merlin panel 3 Alarm relay alarm signal to GDP panel 4 Alarm relay volt free connection Normally closed 5 Alarm relay volt free connection Common 6 Alarm relay volt...
Page 6: ...neral household waste but kept separate for the treatment recovery and recycling of the materials used Please contact your supplier or local authority for details of recycling schemes in your area CON...