PROGRAMMING OBSTACLE SENSOR
OBSTACLE
PROGRAMMING
P6
helps you to program the obstacle detection sensor.
P6
sets:
•
A7
→
Motor A
standard obstacle detection threshold
•
A8
→
Motor A
slowdown obstacle detection threshold
HOW-TO:
1.
The gate must be closed.
2.
Selecting
P6
using buttons A/B.
3.
When display shows
--
press a START command.
4.
The display shows
*1
motor closing pushing on the mechanical stop. The control board has
detected the maximum motor stress when an obstacle is in the path of the gate.
5.
The display shows
*2
motor A opens for 4 seconds. motor stops. The control board has detected
the motors stress without any obstacle.
6.
The display sho
w
s
*3
the gate returns to initial position. When motor stops the procedure is
finished.
If the display shows
9P
an error has occurred during the procedure.
Any command during the steps 2,3,4,5,6 stops
P6
programming and display will show
9P
.
After programming you can modify the obstacle parameters manually. For instance you can disable
slowdown obstacle detection
setting
A8
to
no
.
P6
www.tecnoautomazione.com