Pump

: Pump power in percent. Use the buttons

 / 

 to decrease / increase the power, when the 

output is on.

Errors

When an error is registered, the controller goes to 

shutdown state if it is in Burn state.

The only exception is error 

Overheat Bunker

When it occurs, the controller goes straight to Clean 
state even if the work mode is OFF.

The possible errors are:

Temp sensor

: Temperature sensor (from t1 to 

t4) is either broken or shorted (according to the error 
description).

Ignition failed

: The device failed to ignite.

No pellets

: The pellet level sensor has 

determined that there is no more fuel and refill time 
has expired.

Cleaner

: The cleaner mechanism is not in the 

right position according to the level input sensor (

I3

).

Burning stopped

: In Burn state, a loss of 

flame is detected according to the flue gases 
temperature or light intensity.

Power failure

: The power was cut for time 

exceeding the recovery time.

Feeder blocked

: The current, consumed by 

the feeder is above the threshold.

Fume pressure

: error input 

E2

 activated.

Clock

: Error occurred in the real time clock 

module. Does not force the device shutdown.

Overheat

: Overheating is registered in some of 

the following modules (according to error 
description):

Water

: boiler temperature exceeded the 

maximum.

Flue

: flue gases temperature exceeded 

maximum.

Bunker

: error input 

E1

 activated.

Actions

The possible errors are:

Pow Supply ON

: Device connected to power.

Pow Supply OFF

: Device disconnected from 

power.

Mode ON

: Device switched to ON mode.

Mode AUTO

: Device switched to AUTO mode.

Mode OFF

: Device switched to OFF mode.

Service Menu

: Service menu accessed.

Service

: Device serviced.

16

Service parameters

Summary of Contents for tPell

Page 1: ...tPell Pellet Combustion Controller Version 24 06 20...

Page 2: ...tings 5 Week Timer 6 Info 6 Outputs 6 Date Time 7 Errors Actions 7 Principle of operation 8 Work mode 8 ON AUTO 8 OFF 8 States 8 Clean 8 Ignition 8 Kindle 8 Burn 8 Purge 8 Shutdown 9 Wait 9 Service pa...

Page 3: ...mostat on or off if used Current temperature the measured temperature of the heated object Power the current operating power when burning in kW or relative units Fumes fan revolutions of the fan in Fe...

Page 4: ...In AUTO mode the temperature is fixed by the week timer or the external thermostat Quick menu Fig 5 Quick menu To access the Quick menu press the button from the Main screen For navigation use the but...

Page 5: ...press to save the change or to cancel the modification and revert to the previous value Heating Fig 8 Heating Boiler Temp boiler temperature set point The power is modulated in order to achieve the te...

Page 6: ...decrease increase the temperature by 0 5 C as with by 2 C Info Fig 11 Information On this screen usage information is displayed Pellet counter for the pellets burned from the last reset In order to re...

Page 7: ...creen title in brackets Errors 6 the number of the registered errors is shown Press over selected element to get detailed information about it To switch between views use the buttons Errors The error...

Page 8: ...by monitoring the temperature of flue gases or the flame intensity depending on configuration On successful ignition it passes to the next state If the ignition time runs out before ignition is detec...

Page 9: ...e state However the device will automatically transition to ON mode when the system needs to generate heat The device is in standby awaiting for some of the heated objects to need heating When all the...

Page 10: ...pause Feeder run All parameters listed below that set the feeder time have the meaning of Feeder Fan Max Maximum revolutions per minute of the fumes fan It is used to calculate the percents that set...

Page 11: ...Turn on temperature Pump Min Temp Pump Hyst Turn off temperature Pump Min Temp Pump Hyst Wait DHW ON Temperature difference below the set temperature in order to exit from Wait state Wait DHW OFF Temp...

Page 12: ...e specified the shutdown is started Wait Temp ON Difference between the current and set temperature under which the device immediately transitions from Wait to Burn state Wait Temp OFF Difference betw...

Page 13: ...ignition Exceeding this temperature raise is considered for successful ignition Light Level Light sensor level exceeding it is considered for successful ignition Feeder2 Secondary feeder work time in...

Page 14: ...alue of the parameter is OFF Purge Period Purge period When the device is in Burn state and the set time expires it transitions to Purge state Upon completion it returns back to Burn state The minimum...

Page 15: ...ted and saved After changing the service password you will be asked again for it in order to access the service menu Stop Work Fig 18 Stop Work The device can be forced to stop ignoring the conditions...

Page 16: ...g stopped In Burn state a loss of flame is detected according to the flue gases temperature or light intensity Power failure The power was cut for time exceeding the recovery time Feeder blocked The c...

Page 17: ...ture sensor room temperature thermostat NTC 10K t4 Temperature sensor DHW Light sensitive i1 Light sensor flame intensity Active level GND i2 Hall sensor for fan revolutions counting i3 Capacitive ind...

Page 18: ...Fig 20 Connection 18 Connection...

Page 19: ...h square opening sized 128 x 57 mm To mount the controller first unscrew the mounting bracket then put the controller in the opening Fix it in place by putting the bracket on the back side and fasten...

Page 20: ...term is 24 months from date of sale The guarantee is not valid in following cases Incorrect installation Attempts to make repairs and or modifications of equipment by the customer Visible damages of...

Reviews: