Additional menus
Opto Calibration
Fig 16
Flame sensor calibration
Here you can set the minimum and maximum value
for the light sensor level. They define the limits, that
are used to calculate the flame intensity in percents
(0% =
Min
, 100% =
Max
).
The table shown on display, constitutes of the
following columns:
■
Reading:
▹
Current
: reading of the light sensor in the
current moment
▹
Min
: value set for minimum intensity (0%)
▹
Max
: value set for maximum intensity (100%)
■
Percent from the whole measured range
■
Value in absolute units (from 0 to 4095),
corresponding to the light sensor input voltage (I1).
Use the navigation buttons to choose a parameter to
edit or action:
■
Absolute value Min/Max
– edit the absolute
value, used to set the min/max limits.
■
Current value Min/Max
– choosing some of the
buttons, the according parameter takes the current
value of the light sensor and is saved.
Change Password
Fig 17
Service menu password change
You can change the password for accessing the
service menu from here. Enter a new password two
times, as the second time the password should match
the first one. Only then it will be accepted and saved.
After changing the service password, you will be
asked again for it in order to access the service menu.
Stop Work
Fig 18
Stop Work
The device can be forced to stop, ignoring the
conditions for needed to complete a shutdown
procedure. If the device is working, first a transition to
Clean
state is made, as a repetition of Stop Work
command switches the device to
OFF
mode.
Outputs Test
Fig 19
Outputs test
Warning! Improper activation of the
controller's outputs can lead to dangerous
situation!
Every single one of the controller's outputs can be
manually activated. This screen is only accessible if
the controller is in OFF mode and in Idle state.
Use the buttons
and
to choose an output to
activate. Press
to toggle on and off the current
output. The check box on the right side of the screen
indicates its current condition.
There is additional information, located next to the
check box, for the following outputs:
■
Feeder
: Feeder current consumed, measured
by a current sensing detector in the controller. This
value can be used to establish the normal work
current as well as the block current of the feeder.
■
Fan
: Revolutions per minute measured by the
hall sensor (I2). Tests the correct operation of the
sensor and determines the maximum speed of the fan
installed.
Service parameters
15