Programming with TAPPS2 / CAN bus
31
CAN analogue outputs
Up to 32 CAN analogue outputs can be programmed. They are defined by specifying the
source
in the
bus converter.
Link to the source in the module which supplies the value for the CAN output.
•
DL inputs
•
M-Bus inputs
•
KNX inputs (with fitted module)
•
Modbus inputs (with fitted module)
•
Functions
•
Fixed values
•
System values
Example
: Source: M-Bus input 1
Designation
Every CAN analogue output can be
given its own designation. The
designation can be selected from
various designation groups or can be
user defined.
Transmission condition
Example
:
If change > 10
A new transmission will be made if the current value has changed by more
than the quantity specified (1.0 K in this example) compared to the last
transmitted value. In the module, the unit of the source is applied together
with the corresponding decimal place.
(Minimum value: 1)
Blocking time 00:10
[mm:ss]
If the value changes within 10 seconds of the last transmission by more
than 1.0 K, the value is nevertheless only transmitted again after 10
seconds.
(Minimum value: 1 sec)
Interval time 5 min
The value is transmitted every 5 minutes even if it has not changed by more
than 1.0 K since the last transmission.
(Minimum value: 1 minute)