TECHNICAL DATA

MODELS

POWER RELAY (COMPRESSOR)

FINDER 

OMRON 

FINDER 

OMRON 

OMRON

OMRON 

65.31

G4F

65.31

G4F

G7L

G4F

P.C.B.

Type

RY1

RY1.1

RY1

RY1.1

RY1

RY1.1

Coil tension

230V~50Hz

12Vdc

230V~50Hz

12Vdc

230V~50Hz

12Vdc

Coil resistance (20°C)

7.250±10%

158±10%

7.250±10%

158±10%

21.000±15%

158±10%

Contact rating

30A-250V

20A-250V

30A-250V

20A-250V

25A-250V

20A-250V

COMPRESSOR

(CM)

Model
Nominal input (230V)

W

Compressor oil

cc

Coil resistance (20°C)

C-R

C - R                

C-S       

SAFETY DEVICE

(OLR)

Operanting temperature

Open
Close

Operanting amperes

Open

(Room temperature 25°C)
Operanting temperature

(OLR 1)

Open
Close

Operanting temperature

(OLR 2)

Open
Close

Operanting temperature

Open

(Room temperature 25°C)

RUN CAPACITOR

(C3)

Capacity

µF

Power supply

V~

RUN CAPACITOR

(C4) COMPRESSOR

Capacity

µF

Power supply

V~

POWER RELAY

(RA) COMPRESSOR

Type
Coil tension

V~

Coil resistance (20°C)

k

Contacts rating
Operating voltage
Operating voltage

CURRENT LIMITER

(LC)

Type
Coil resistance (20°C)

Induttance ( a 19A~50Hz)

mH

HEAT EXCHANGER

Coils
Rows
Fin pitch

mm

Face area

SMDV11XC5

500

3,01±7%

550

1,92÷1,84±7%

5,28÷7,1±7%

MRA990003-9201

MST20ALU-9201

3,31±7%

7,82±7%

7,35±7%

500

in 6÷16 sec.

135±5°C
69±11°C

 19A 

in 6÷16 sec.

140±5°C

 22,5A 

in 6÷16 sec.

CS-7C115

115±4°C
95±10°C

MST56ALU

80235245B

1290

COMPRESSOR

150±5°C
69±11°C

830

950

80225245B

80228245B

22,5

450

20

450

2

3

3

60÷120V~

R143C

690±5%

14

Alluminium fin / Copper tube

EVAPORATOR COIL

1,8

0,118

300V~50Hz

330

AMVL300C

25

450

69±11°C

 16A 

SMDV9XC5

SMDV14XC5

IF EQUIPED

IF EQUIPED

IF EQUIPED

13,150±2%

20A 

185÷217V~

56

5

Summary of Contents for SMDV11XC5

Page 1: ...08180012 2 03 2003 TECHNICAL DATA SERVICE MANUAL MODELS WITH R407C SMDV...

Page 2: ...IC CIRCUIT INTERRUPTED 3 MINUTES AFTER ON IS PRESSED 10 FAN MOTOR DOES NOT WORK WHILE ON BUTTON IS PRESSED 10 FAN MOTOR WORKS AT ONE SPEED ONLY FMI 11 POOR COOLING 11 FAN MOTOR WORKS NORMALLY BUT THE...

Page 3: ...0 1040 Refrigerant control Noise level Lp NOTE 3 INT high low dB A 44 40 44 40 47 45 EXTERNAL dB A 48 48 41 Flexible tube lenght m 2 5 m DIMENSIONS WEIGHT Internal unit Height mm 800 Width mm 470 Dept...

Page 4: ...368 5 15 C 781 5 35 C 290 5 20 C 604 5 40 C 230 5 25 C 470 5 50 C 147 5 FAN FAN MOTOR FMI M01582 Cross Flow Dimensions mm 125 x 295 Power supply 230V 50Hz N of poles 4 High low speed rpm 1150 870 1180...

Page 5: ...m temperature 25 C RUN CAPACITOR C3 Capacity F Power supply V RUN CAPACITOR C4 COMPRESSOR Capacity F Power supply V POWER RELAY RA COMPRESSOR Type Coil tension V Coil resistance 20 C k Contacts rating...

Page 6: ...RNATIVE MOTOR FMO 40101243 L 40101243 L Nominal input 230V W 70 70 Coil resistance 20 C BLU BRN BLU BRN 203 7 203 7 BLU BLK BLU BLK 201 7 201 7 safety device Thermostat Thermostat Setting OPEN C 150 1...

Page 7: ...f the room temperature is 1 C above the set temperature the compressor starts working if this has been OFF for at least 3 minutes 3 If the room temperature is the same or under the set temperature the...

Page 8: ...5 20 25 30 35 40 45 50 EXTERNAL TEMPERATURE C OPERATING CURRENT A 21 C 27 C 32 C SMDV97C5 3 3 2 3 4 3 6 3 8 4 4 2 4 4 4 6 4 8 5 20 25 30 35 40 45 50 EXTERNAL TEMPERATURE C OPERANTING CURRENT A 21 C 27...

Page 9: ...c Check if the pilot NO Is the flickering alarm control CE lamp is burnt lamp on the control Eventually replace panel not visible it ELECTRIC CIRCUIT INTERRUPTED WHEN ON BUTTON IS PRESSED Check the un...

Page 10: ...ace the NO FMO Check if compressor CM outdoor fan motor works FAN MOTOR FMI DOES NOT WORK WHILE ON BUTTON IS PRESSED Disconnect the unit from line Check if the fan motor is well fitted and if the blad...

Page 11: ...inding values FMI YES Replace fan motor FMI POOR COOLING Is the unit cooling capacity NO Suggest a more power suitable for the room ful unit thermal loads YES Are both air filters and heat NO Clean fi...

Page 12: ...itor C tor capacity C continuity TH sensor TH on electronic control CE YES terminal blocks YES Replace the NO Check the com Check electronic compressor pressor winding control CE continuity OUTDOOR FA...

Page 13: ...3 minutes Is relay compressor coil power NO already elapsed since on NO supplied RC operation YES YES Replace NO Check if relay Is the thermostat properly NO Properly adjust relay RC contact is close...

Page 14: ...F THERMOFUSE B BLU BLUE RE ELECTRIC HEATER TS SAFETY THERMOSTAT M BRN BROWN MVx FMx FAN MOTOR P PROGRAMMER G V GRN YEL GREEN YELLOW K ORL OVERLOAD PROTECTOR RP PUMP RELAY A ORG ORANGE CE ELECTRONIC CO...

Page 15: ...RIC HEATER TS SAFETY THERMOSTAT M BRN BROWN MVx FMx FAN MOTOR P PROGRAMMER G V GRN YEL GREEN YELLOW K ORL OVERLOAD PROTECTOR RP PUMP RELAY A ORG ORANGE CE ELECTRONIC CONTROL IM MOTOR IMPEDANCE R RED R...

Reviews: