TECHNICAL DATA

INDOOR UNIT COMPONENTS SPECIFICATION

MODEL

SMDV9XC5

SMDV11XC5

SMDV14XC5

CONTROLLER P.C.B.

(CE)

RY1 SPLIT / RY1.1 SPLIT

Controls
Thermostat 

Setting 

 °C

15 ± 1,5°C ÷ 31 ± 2°C

Differential

 °C

0,9 ± 0,2°C

Starting delay time

3min. ± 10sec.

Function selection and indicator lamps

Frosting prevention

OPEN

°C

1 ± 1°C

CLOSE

°C

6 ± 1°C

Transformer

Power

1,5VA

Primary

220V

Secondaty

10,5V

Primary resistance

 20°C  2754 

±10%

Secondary resistance

 20°C

 17,1 

±10%

COIL TEMPERATURE SENSOR

(TH1)

NTC 

Resistance

k

        -20°C 5846±5% ; 20°C 604±5% 
        -10°C 3159±5% ; 30°C 368±5% 
           0°C 1766±5% ; 40°C 230±5% 
         10°C 1018±5% ; 50°C 147±5% 

AIR TEMPERATURE SENSOR

(TH2)

NTC 

Resistance

k

         10°C 1018±5% ; 30°C 368±5% 
         15°C   781±5% ; 35°C 290±5% 
         20°C   604±5% ; 40°C 230±5% 
         25°C   470±5% ; 50°C 147±5% 

FAN & FAN MOTOR

(FMI)

M01582

Cross - Flow

Dimensions

mm

Ø 125 x 295

Power supply

230V~50Hz

N° of poles

4

High/low speed

rpm

1150/870

1180/950

1260/1040

Nominal input (230V)

W

36

Coil resistance (20°C)

GRY-WHT : 392 ± 5%

WHT-YEL : 213 ± 5%

YEL-PNK : 66 ± 5%

GRY-BRN : 163 ± 5%

Safety device

Internal thermostat

Setting:

open

150±10

close

Automatic

RUN CAPACITOR

(C1)

INDOOR FAN MOTOR

Capacity

µF

0,6

0,6

1

Tension

V~

440

440

440

CONDENSER PUMP

(PC)

PC 95643

Power supply

230V~50Hz

Nominal input (230V)

W

12±10%

Coil resistance (20°C)

122±10%

PUMP RELAY

(RP)

-

-

FINDER 60.62

Coil power

-

-

230V~50Hz

Coil resistance (20°C)

k

-

-

7,250±10%

Contact rating

-

-

10A - 250V

FLOAT MICROSWITCH

CROUZET F83161.3

Contact rating

10(4)A - 250VAC

Float           

up

Open

Down

Close

Electronic microprocessor

COOLING / FAN

HIGH/LOW speed

ALARM lamp

ON / OFF

4

Summary of Contents for SMDV11XC5

Page 1: ...08180012 2 03 2003 TECHNICAL DATA SERVICE MANUAL MODELS WITH R407C SMDV...

Page 2: ...IC CIRCUIT INTERRUPTED 3 MINUTES AFTER ON IS PRESSED 10 FAN MOTOR DOES NOT WORK WHILE ON BUTTON IS PRESSED 10 FAN MOTOR WORKS AT ONE SPEED ONLY FMI 11 POOR COOLING 11 FAN MOTOR WORKS NORMALLY BUT THE...

Page 3: ...0 1040 Refrigerant control Noise level Lp NOTE 3 INT high low dB A 44 40 44 40 47 45 EXTERNAL dB A 48 48 41 Flexible tube lenght m 2 5 m DIMENSIONS WEIGHT Internal unit Height mm 800 Width mm 470 Dept...

Page 4: ...368 5 15 C 781 5 35 C 290 5 20 C 604 5 40 C 230 5 25 C 470 5 50 C 147 5 FAN FAN MOTOR FMI M01582 Cross Flow Dimensions mm 125 x 295 Power supply 230V 50Hz N of poles 4 High low speed rpm 1150 870 1180...

Page 5: ...m temperature 25 C RUN CAPACITOR C3 Capacity F Power supply V RUN CAPACITOR C4 COMPRESSOR Capacity F Power supply V POWER RELAY RA COMPRESSOR Type Coil tension V Coil resistance 20 C k Contacts rating...

Page 6: ...RNATIVE MOTOR FMO 40101243 L 40101243 L Nominal input 230V W 70 70 Coil resistance 20 C BLU BRN BLU BRN 203 7 203 7 BLU BLK BLU BLK 201 7 201 7 safety device Thermostat Thermostat Setting OPEN C 150 1...

Page 7: ...f the room temperature is 1 C above the set temperature the compressor starts working if this has been OFF for at least 3 minutes 3 If the room temperature is the same or under the set temperature the...

Page 8: ...5 20 25 30 35 40 45 50 EXTERNAL TEMPERATURE C OPERATING CURRENT A 21 C 27 C 32 C SMDV97C5 3 3 2 3 4 3 6 3 8 4 4 2 4 4 4 6 4 8 5 20 25 30 35 40 45 50 EXTERNAL TEMPERATURE C OPERANTING CURRENT A 21 C 27...

Page 9: ...c Check if the pilot NO Is the flickering alarm control CE lamp is burnt lamp on the control Eventually replace panel not visible it ELECTRIC CIRCUIT INTERRUPTED WHEN ON BUTTON IS PRESSED Check the un...

Page 10: ...ace the NO FMO Check if compressor CM outdoor fan motor works FAN MOTOR FMI DOES NOT WORK WHILE ON BUTTON IS PRESSED Disconnect the unit from line Check if the fan motor is well fitted and if the blad...

Page 11: ...inding values FMI YES Replace fan motor FMI POOR COOLING Is the unit cooling capacity NO Suggest a more power suitable for the room ful unit thermal loads YES Are both air filters and heat NO Clean fi...

Page 12: ...itor C tor capacity C continuity TH sensor TH on electronic control CE YES terminal blocks YES Replace the NO Check the com Check electronic compressor pressor winding control CE continuity OUTDOOR FA...

Page 13: ...3 minutes Is relay compressor coil power NO already elapsed since on NO supplied RC operation YES YES Replace NO Check if relay Is the thermostat properly NO Properly adjust relay RC contact is close...

Page 14: ...F THERMOFUSE B BLU BLUE RE ELECTRIC HEATER TS SAFETY THERMOSTAT M BRN BROWN MVx FMx FAN MOTOR P PROGRAMMER G V GRN YEL GREEN YELLOW K ORL OVERLOAD PROTECTOR RP PUMP RELAY A ORG ORANGE CE ELECTRONIC CO...

Page 15: ...RIC HEATER TS SAFETY THERMOSTAT M BRN BROWN MVx FMx FAN MOTOR P PROGRAMMER G V GRN YEL GREEN YELLOW K ORL OVERLOAD PROTECTOR RP PUMP RELAY A ORG ORANGE CE ELECTRONIC CONTROL IM MOTOR IMPEDANCE R RED R...

Reviews: