The use of portable telephones near the air-conditioner
may cause disturbance to its normal operation and must
be avoided. In case abnormal operation is noticed,
(OPERATION lamp lights but outdoor unit will not run) to
restore normal operation turn-off electric supply for 60
seconds at least, by disconnecting the main switch or
the wall plug, then start again the air-conditioner.

The blinking OPERATION lamp, together with the stop of
the air conditioner for a short time are due to the exceeding
condensate drainage. 
If the OPERATION lamp goes on blinking and the air
conditioner definitely stops means that the condensate
pump is not working or that the condensate drain pipe in
the flexible connection pipe is obstructed; in this case
contact the AFTER SALE SERVICE.
In case of emergency the air conditioner can work by
draining the condensate from the back little pipe into a
rather short container: extract the little pipe and remove
the cap.

If your air conditioner does not work properly, first check
the following points before requesting service.
If it still does not work properly, contact your dealer or
service center.

Trouble: the air conditioner does not run at all.
Possible cause:
1. Power failure.
2. Leakage breaker tripped.
3. Line voltage is too low.
4. Operation button is OFF.
5. Batteries in remote control unit have run down.

Remedy:
1. Restore power.
2. Contact service center.
3. Consult your electrician or dealer.
4. Press the button again.
5. Replace batteries.

Trouble: The air conditioner does not operate and
STANDBY lamp flashes.

TIPS FOR ENERGY SAVING

DO NOT:

Block the air intake and outlet of the unit. 
If they are obstructed, the unit will not work well, and
may be damaged.

Let direct sunlight into the room. Use sunshades, blind
or curtain.

DO:

Always try to keep the air filter clean. A clogged filter
will impair the performance of the unit.

To prevent conditioned air from escaping, keep windows,
doors and any other openings closed.

13

TROUBLESHOOTING

Possible cause:
1. Air conditioner room sensor defective.
Remedy:
1. Contact service centre.

Trouble: STANDBY and OPERATION lamps flash and the
air conditioner does not operate.
Possible cause:
1. Air conditioner coil sensor defective.
Remedy:
1. Contact service centre.

Trouble: Compressor runs but soon stops.
Possible cause:
1. Obstruction in front of condenser coil.
Remedy:
1. Remove obstruction.

Trouble: Poor cooling or heating performance.
Possible cause:
1. Dirty or clogged air filter.
2. Heat source or many people in room.
3. Doors and/or windows are open.
4. Obstacle near air intake or air discharge port.
5. Thermostat is set too high (for cooling) or too low (for

heating).

6. Outdoor temperature is too low (heat pump version).
7. Defrosting system does not work (heat pump version).
Remedy:
1. Clean air filter to improve airflow.
2. Eliminate heat source if possible.
3. Shut them to keep the heat or cold out.
4. Remove it to ensure good airflow.
5. Set the temperature lower (or higher).
6. Try to use a back-up heater (heat pump version).
7. Consult your dealer (heat pump version).

Trouble: Clicking sound is heard from the air conditioner.
Possible cause:
1. In heating or cooling operation, any plastic parts may

expand or shrink due to a sudden temperature change.
In this event, a clicking sound may occur.

Remedy:
1. This is normal, and the sound will disappear when an

even temperature is settled.

WARNING

EG

NOTE

The blinking of OPERATION, TIMER and STANDBY lamps,

indicates that the operating mode selected (          ) is not

compatible with the unit. If this happen the air conditioner

does not operate until the correct mode is selected.

Summary of Contents for SCDF Series

Page 1: ...r Condicionado com condensador remoto K Kl li im ma at ti is st ti ik ko o k kl le ei is st tw wn n c cw wr rw wn n m me e s su um mp pu uk kn nw wt th h EG I F D E P COOL DRY FAN COOL DRY HEAT FAN GR OPERATING INSTRUCTIONS ISTRUZIONI D USO NOTICE D UTILISATION BEDIENUNGSANLEITUNG INSTRUCCIONES DE USO INSTRUCÇÕES DE FUNCIONAMENTO O OD DH HL LI IE ES S C CR RH HS SE EW WS S COOL DRY FAN MOVABLE AIR...

Page 2: ... practice which can result in severe personal injury or death This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage WARNING CAUTION EG COOL DRY FAN COOL DRY HEAT FAN COOLING OUTDOOR TEMPERATURE 46 C D B ROOM TEMPERATURE 32 C D B 23 C W B OUTDOOR TEMPERATURE 19 C D B ROOM TEMPERATURE 19 C D B 14 C W B OPERATING LIMITS HEATING OUTDOOR TEM...

Page 3: ... exceeding condensate drainage or because of malfunctioning of the condensate drainage system EG The OFF position does not disconnect the power Use the main power switch to turn off power completely WARNING WATER LEVEL ALARM 3 5 Operation button without remote control Push the button to walk through the OFF COOL and HEAT operation modes PRODUCT IDENTIFICATION 10 2 7 11 5 6 1 8 3 4 9 13 4 3 7 5 12 ...

Page 4: ... max absorbed powers Install a double pole switch protected fuses of the delayed type upstream the electricity wall socket 10A 4 ELECTRICAL REQUIREMENTS INSTALLATION LOCATION Do not install this air conditioner where there are fumes or flammable gases or in an extremely humid space such as a green house Do not install the air conditioner where excessively high heat generating objects are placed Do...

Page 5: ...x the basket to the wall below the window sill 2 Place the unit in the basket and check that it is levelled INSTALLATION TYPE C USING THE SUPPORT 1 Fix the support guide to the wall below the window sill 2 Insert the support in the handle of outdoor unit and turn the outdoor unit upside down as shown in the picture 3 Place the support and secure it at the edge of the unit using the screws 4 Insert...

Page 6: ...ER HEAD EG Insert two AAA alkaline batteries of 1 5 V DC making sure that point in the direction marked in the battery compartment The displayed time flashes Press the SEL TYPE button Remote controller is now ready for operation The batteries last about six months Depending on how much you use the remote control unit Remove the batteries if you do not use the remote control unit for more than one ...

Page 7: ...mer For details refer to paragraphs SETTING THE HOUR and SETTING THE TIMER2 ON OFF BUTTON This button turns the air conditioner ON and OFF TIMER SEL BUTTON Premendo il pulsante sul display viene attivata la procedura per l impostazione del timer Per dettagli vedere esempio REGOLAZIONE DEL TIMER DISPLAY Information is displayed when the remote controller is switched on If switched off only the oper...

Page 8: ...is low frost or ice may appear on the heat exchanger coil reducing the heating performance When this happens a microcomputer defrosting system operates At the same time the fan in the indoor unit stops and the STANDBY lamp remains lit until defrosting is completed Heating operation restarts after several minutes This interval will vary slightly depending on the room and outdoor temperature HEATING...

Page 9: ...NIGHT function What does the NIGHT mode mean In this mode the air conditioner will cool or heat the room to the set temperature and then the thermostat will make the unit pause After about 1 hour the air conditioner will automatically reset the set temperature as follows also refer to graphs OPERATING MODE SET TEMPERATURE CHANGE Heating Lowered by 1 C Cooling and Dehumidifying Raised by 1 C When t...

Page 10: ... SET H button until the designed hour is displayed Press the SET M button until the designed minutes are displayed The display will change automatically back to show the present time after 10 sec 3 Press the ON OFF button to start the air conditioner 4 Press the TIMER SEL button to activate the ON timer B HOW TO SET THE OFF TIME 1 Press the SEL TYPE button twice The OFF and time indications flash ...

Page 11: ...TDOOR UNIT CASING AND CONDENSING COIL CAUTION INDOOR UNIT TEST OFF ON AIR FILTER The air filter must be cheked at least once every two weeks operation Operation with a dirty filter always causes a lower efficency of the air conditioner and severe product damage The filter is located at the back of the intake grille in the front of the air conditioner and shall be removed from the upper side of the...

Page 12: ... OR SUPPORT GUIDE KIT FOR OUTDOOR UNIT If you want to utilise the air conditioner in several rooms it is possible to buy varies baskets or support guides for the installation of outdoor unit 2 holes ø 10 200 210 50 2 holes ø 10 100 min 200 SUPPORT GUIDE BASKET ...

Page 13: ...be damaged Let direct sunlight into the room Use sunshades blind or curtain DO Always try to keep the air filter clean A clogged filter will impair the performance of the unit To prevent conditioned air from escaping keep windows doors and any other openings closed 13 TROUBLESHOOTING Possible cause 1 Air conditioner room sensor defective Remedy 1 Contact service centre Trouble STANDBY and OPERATIO...

Page 14: ...A ESTERNA UNITÉ EXTÉRIEURE AUßENEINHEITEN UNIDADES EXTERNAS EXWTERIKES MONADES FMO OUTDOOR FAN MOTOR MOTORE ESTERNO VENTOLA MOTEUR DE VENTILATEUR EXTÉRIEUR AUSSENLÜFTERMOTOR MOTOR EXTERIOR DE LATURBINA EXWTERIKOS ANEMISTHRAS FMI INDOOR FAN MOTOR MOTORE INTERNO VENTOLA MOTEUR DE VENTILATEUR INTÉRIEUR INNENLÜFTERMOTOR MOTOR INTERIOR DE LATURBINA ESWTERIKOS ANEMISTHRAS IND ASSY INDICATOR ASSY GRUPPO ...

Page 15: ...GWP 1975 Zerstreuen Sie R410A in Atmosphäre nicht R410A ist ein fluoriertes Gas abgedeckt durch Kyoto Protokoll mit einem globalen wärmenden Potential GWP 1975 No expulsar R410A a la atmósfera el R410A es un gas fluorado de efecto invernadero cubierto por el protocolo de Kyoto con potencial de calentamiento global GWP 1975 Não exale R410A na atmosfera R410A é um fluorinated gás coberto pelo protoc...

Page 16: ...S A C Printed in italy R D 28 Reyrieux BP 131 01601 Trévoux CEDEX France Tél 04 74 00 92 92 Fax 04 74 00 42 00 R C S Bourg en Bresse B 759 200 728 ...

Reviews: