– 7 –
MODEL No. Indoor Unit SPA480R5TAA
Outdoor Unit GR480R7TAA
POWER SOURCE 380 - 400 - 415 V / 3N / 50 Hz
PERFORMANCE Cooling Heating
Capacity kW
14 16
BTU / h
47,800 54,600
Air circulation (Hi/Me/Lo) m3 / h 1,920/1,610/1,320
Moisture removal(High) Liters/h 7.1 -
ELECTRICAL RATINGS
Voltage rating V 380 400 415 380 400 415
Available voltage range V
342 - 456 342 - 456
Running amperes* A 8.5 8.7 8.9 9 9.1 9.2
Max. running amperes** A 9.1 9.1 9.3 9.8 9.5 9.2
Power input kW 4.84 5.04 5.13 5.19 5.33 5.41
Power factor % 86.5 83.6 80.2 87.6 84.5 81.8
C.O.P W / W 2.89 2.78 2.73 3.08 3 2.96
Max. starting amperes A
71 73 75 71 73 75
FEATURES
Controls / Thermostat control Microprocessor / I.C. thermostat
Timer ON / OFF 72-hours / ON/OFF 24-hours & Program
Fan speeds Indoor/Outdoor 3 and Automatic control/ 2 (Auto)
Airflow direction (Indoor) Automatic (Remote control)
Air filter Washable, easy access
Remote controller (Option) Wired : K70D026ZAA / Wireless : K70D027ZAA
Refrigerant control Electronic Refrigerant Control Valve
Drain pump (drain connection) No (20A, OD26mm)
Compressor Scroll
Operation sound
Indoor - Hi/Me/Lo dB - A
48 / 44 / 40
Outdoor - Hi dB - A
55
REFRIGERANT TUBING
Limit of tubing length m (ft.)
50 (164)
Limit of tubing length at shipment m (ft.)
30 (98)
Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit: 50 (164)
between the two units Outdoor unit is lower than indoor unit: 30 (98)
Refrigerant tube Narrow tube mm (in)
9.52 ( 3 / 8 )
outer diameter Wide tube mm (in)
19.05 ( 3 / 4 )
Refrigerant amount at shipment kg
R22 - 4.5
DIMENSIONS & WEIGHT Indoor unit Outdoor unit
Unit dimensions Height mm (in) 250 (9-27/32) 1,235 (48-20/32)
Width mm (in) 1,570 (61-26/32) 940 (37)
Depth mm (in) 670 (26-12/32) 340 (13-12/32)
Package dimensions Height mm (in) 336 (13-7/32) 1,326 (52-7/32)
Width mm (in) 1,670 (65-24/32) 1,016 (40)
Depth mm (in) 782 (30-25/32) 416 (16-12/32)
Net weight kg (lb) 41 (90) 108 (238)
Shipping weight kg (lb) 51 (112) 115 (254)
Shipping volume m
3
(Cu. ft.) 0.439 (15.5) 0.56 (19.8)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Cooling :
Rating conditions(*) : Indoor air temperature 27
°
C DB / 19
°
C WB, Outdoor air temperature 35
°
C DB
Heating :
Rating conditions(*) : Indoor air temperature 20
°
C DB, Outdoor air temperature 7
°
C DB / 6
°
C DB
1-1 Unit Specifications
1 . SPECIFICATIONS