– 4 –
MODEL No. Indoor Unit SPA250R5TAA
Outdoor Unit GR250R5TAA
POWER SOURCE 220 - 230 - 240 V / 1 Phase / 50 Hz
PERFORMANCE Cooling Heating
Capacity kW 7.3 8
BTU / h 25,000 27,000
Air circulation (Hi/Me/Lo) m3 / h 1,140/1,020/840
Moisture removal(High) Liters/h 3.4 -
ELECTRICAL RATINGS
Voltage rating V 220 230 240 220 230 240
Available voltage range V 198 - 264 198 - 264
Running amperes* A 14.7 14.9 15 14.8 14.8 15
Max. running amperes** A 16.9 16.8 16.8 16.1 15.9 15.8
Power input kW 3.11 3.15 3.2 3.11 3.15 3.2
Power factor % 96.2 91.9 88.9 95.5 92.5 88.9
C.O.P W / W 2.35 2.32 2.28 2.57 2.54 2.5
Max. starting amperes A 68 71 74 68 71 74
FEATURES
Controls / Thermostat control Microprocessor / I.C. thermostat
Timer ON / OFF 72-hours / ON/OFF 24-hours & Program
Fan speeds Indoor/Outdoor 3 and Automatic control/ 2 (Auto)
Airflow direction (Indoor) Automatic (Remote control)
Air filter Washable, easy access
Remote controller (Option) Wired : K70D026ZAA / Wireless : K70D027ZAA
Refrigerant control Electronic Refrigerant Control Valve
Drain pump (drain connection) No (20A, OD26mm)
Compressor Rotary
Operation sound
Indoor - Hi/Me/Lo dB - A
45 / 41 / 37
Outdoor - Hi dB - A
52
REFRIGERANT TUBING
Limit of tubing length m (ft.)
50 (164)
Limit of tubing length at shipment m (ft.)
30 (98)
Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit: 50 (164)
between the two units Outdoor unit is lower than indoor unit: 30 (98)
Refrigerant tube Narrow tube mm (in)
6.35 (1 / 4)
outer diameter Wide tube mm (in)
15.88 (5 / 8)
Refrigerant amount at shipment kg
R22 - 3.0
DIMENSIONS & WEIGHT Indoor unit Outdoor unit
Unit dimensions Height mm (in) 185 (7-9/32) 735 (28-30/32)
Width mm (in) 1,270 (50) 940 (37)
Depth mm (in) 670 (26-12/32) 340 (13-12/32)
Package dimensions Height mm (in) 271 (10-21/32) 826 (32-17/32)
Width mm (in) 1,370 (53-30/32) 1,016 (40)
Depth mm (in) 782 (30-25/32) 416 (16-12/32)
Net weight kg (lb) 28 (62) 71 (157)
Shipping weight kg (lb) 36 (79) 77 (170)
Shipping volume m
3
(Cu. ft.) 0.29 (10.2) 0.349 (12.3)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Cooling :
Rating conditions(*)
: Indoor air temperature 27
°
C DB / 19
°
C WB, Outdoor air temperature 35
°
C DB
Heating :
Rating conditions(*) : Indoor air temperature 20
°
C DB, Outdoor air temperature 7
°
C DB / 6
°
C DB
1. SPECIFICATIONS
1-1 Unit Specifications