5.5 - REMOTE CONTROL
(exclusively for cooling only models)
5.5.1 - PRESENTATION
Manual remote control - K 60 D 016 Z
S1 On/Off switch.
S2 Ventilation speed selector switch.
S3 Function selector switch.
B1 Room thermostat.
Automatic remote control - K 60 D 025 Z
Optional: a remote temperature sensor K 60 D 028 Z (simple) or K 60 D 033 Z (box) may be connected (see documentation
supplied with the sensors).
S1 ON/Off switch.
S2 Ventilation speed selector switch.
B1 Room thermostat.
5.5.2 - INSTALLATION OF THE BOX
A - PLACEMENT
• Approximately 1.50 m above floor.
• The box must be:
- easily accessible,
- unobstructed (away from curtains, cabinet, shelving,...).
• Avoid:
- any direct sunlight on the box (for example, opposite a window),
- exposure to drafts,
- placing the unit directly in the path of air blown by the air conditioner,
- fixing it on a badly insulated external wall,
- fixing it on a lightweight partition which can vibrate.
B - MOUNTING
• To remove the cover from the box, remove the thermostat knob and unscrew the mounting screw located behind it.
• Attach the base to the wall.
• Route the wiring through the back or from underneath the unit.
5.5.3 - ELECTRICAL CONNECTION
• Make the electrical connection with cable at least 0.75 mm
2
(cable not supplied).
• Make the connections onto the terminal strip as shown in the wiring diagram in paragraph 12 (cable H ).
NOTE:
The control circuit for CP 188 C and 268 X models is protected by a 5 x 20 - 4 A - 250 V fuse (rated breaking power: 63 A)
located in the PA (see schematic diagrams).