Temperature
°
C
Rated ohmic value k
Ω
Ω
Ω
Ω
Ω
- 10
-
5
0
+ 5
+ 10
+ 15
+ 20
+ 25
+ 30
+ 35
187.034
142.602
109.587
85.279
66.785
52.330
41.272
33.000
26.281
21.137
Dimensions:
Width : 130.5 mm
Height : 85 mm
Depth : 31 mm
8.2.2 - REMOTE CONTROL
A - FRONT PANEL
• Keys:
1 - Increase temperature set-point.
2 - Decrease temperature set-point.
3 - Air-conditioner operating mode selector.
4 - Ventilation operating mode selector.
• LED lights:
5 - Set-point temperature.
6 - Signalling (option).
7 - Operation in heating mode.
8 - Operation in cooling mode.
9 - "Standby" operating mode.
10 - "Automatic" operating mode (heating or cooling).
11 - "Ventilation only" operating mode.
12 - "Cooling only" operating mode.
13 - "Heating only" operating mode.
14 - "Automatic ventilation" mode.
15 - "Manual ventilation" mode (3 speeds).
B - INSIDE:
• Adjustment of differentials (see details in § 8-3):
- The neutral zone (between heating cut-off and cooling cut-
off) is adjusted in the factory at 1K. P2 enables adjustment
up to 5 K.
- The difference between the triggering of the
thermodynamic heating and the possible make-up heating
is adjusted in the same way by P1.
- P3 is not used.
The adjustment of the potentiometers can only be done by
steps of 1 K. To do this, adjust the potentiometers on marks 1,
2, 3, 4 or 5.
For the intermediate positions, the electronics automatically
select the following whole value.
8.2.3 - TEMPERATURE SENSORS
Type CTN - 33 k
Ω
Ω
Ω
Ω
Ω
(
±
5%) at 25
°
C
8.3 - OPERATION
8.3.1 - TEMPERATURE ADJUSTMENT OPERATING
DIAGRAM
• Hysterisis of control signals: 0.6
K
to 1
K
• Set-point tolerance:
±
2.5
K
• Tolerance of neutral zone:
±
0.3
K
NOTE:
The cycle inversion valve is activated in heating mode.
Microprocessor
Connection pins
Temperature sensor
Potentiometer
Adjustment of differentials
BCD switch of programs
(for electric heating, set to position 0)
MS
MS
HS
HS
LS
LS
Set-point
Valve
control
Compressor
control
in cooling
Compressor
control
in heating
Control of
possible
make-up
Ventilation control
in automatic mode
Boost
triggering differential
adjustable from
1 to 5K by P1
Neutral zone
adjustable from 1 to 5K by P2