GB
2
2
Ratings and technical data of CAW fan coil units with 1 heat exchanger
Model
3P2
4P2
5P2
Speed
1
2
3
4
1
2
3
4
1
2
3
4
Total cooling capacity (1)
kW
1,24
2,15
2,35
2,60
1,70
3,50
4,00
4,60
2,46
3,80
4,42
5,06
Sensible cooling capacity (1)
kW
0,92
1,78
2,00
2,23
1,15
2,63
3,06
3,56
1,82
2,87
3,33
3,80
Water fl ow (1)
l/h
213
368
404
445
291
600
687
789
422
653
758
869
Pressure drop (1)
kPa
3
8
9
11
3
11
14
17
7
14
18
23
Heating capacity (2)
kW
1,55
2,83
3,11
3,49
1,87
4,35
4,85
5,70
3,35
5,33
6,14
6,75
Pressure drop (2)
kPa
3
7
8
10
3
10
13
17
6
14
18
23
Heating capacity (3)
kW
2,02
3,72
4,09
4,61
2,42
5,7
6,32
7,46
4,46
7,11
8,17
8,91
Water fl ow (3)
l/h
175
323
355
400
210
495
549
648
387
617
710
774
Pressure drop (3)
kPa
2
6
7
8
2
7
9
12
5
12
16
18
Water content
dm3
0,43
0,86
0,86
Air fl ow
m3/h
180
400
460
520
200
530
630
750
370
630
760
880
Power input
W
5
10
12
15
8
24
28
36
12
34
40
46
Sound power level (4)
dB/A
30
41
44
46
32
48
51
55
41
53
57
61
Sound pressure level (5)
dB/A
25
36
39
41
27
43
46
50
36
48
52
56
Water connections
inches
1 / 2
1 / 2
1 / 2
Unit dimensions H x L x P
mm
273 x 575 x 575
273 x 575 x 575
273 x 575 x 575
Grille dimensions H x L x P
mm
64 x 730 x 730
64 x 730 x 730
64 x 730 x 730
Ratings and technical data of CAW fan coil units with 1 heat exchanger
Model
6P2
8P2
10P2
Speed
1
2
3
4
1
2
3
4
1
2
3
4
Total cooling capacity (1)
kW
4,20
5,00
5,40
6,00
5,50
6,50
8,00
9,10
6,23
8,09
8,90
9,92
Sensible cooling capacity (1)
kW
3,13
3,70
3,99
4,40
4,11
5,08
6,10
6,84
4,69
6,17
6,87
7,71
Water fl ow (1)
l/h
720
859
930
1.029
944
1.116
1.373
1.561
1.070
1.389
1.529
1.702
Pressure drop (1)
kPa
16
22
25
30
21
28
41
51
27
42
50
60
Heating capacity (2)
kW
5,40
6,40
7,10
7,70
6,28
8,52
9,42
10,19
7,34
9,53
10,59
11,69
Pressure drop (2)
kPa
15
21
25
30
21
29
39
48
26
42
49
60
Heating capacity (3)
kW
7,08
8,39
9,33
10,08
8,14
11,24
12,26
13,18
9,52
12,34
13,73
15,11
Water fl ow (3)
l/h
615
729
810
875
707
976
1.065
1.145
827
1.072
1.192
1.312
Pressure drop (3)
kPa
12
16
19
22
12
21
24
27
16
26
31
37
Water content
dm3
1,00
1,50
1,50
Air fl ow
m3/h
850
1.060
1.160
1.300
830
1190
1.270
1.400
1.200
1.700
1.980
2.300
Power input
W
13
20
25
41
15
22
41
55
22
36
43
64
Sound power level (4)
dB/A
43
48
49
51
37
46
50
53
43
49
53
57
Sound pressure level (5)
dB/A
38
43
44
46
32
41
45
48
38
44
48
52
Water connections
inches
3 / 4
3 / 4
3 / 4
Unit dimensions H x L x P
mm
273 x 776 x 776
290 x 1066 x 776
290 x 1066 x 776
Grille dimensions H x L x P
mm
64 x 860 x 860
64 x 1150 x 860
64 x 1150 x 860
NOTES CAW WITH 2 PIPES:
1
= water temperature 7/12°C, air temperature dry bulb 27°C, wet
bulb 19°C
2
= inlet water temperature 50°C, water fl ow rate same as in cool-
ing mode, air inlet temperature 20°C
3
= water temperature 60/50°C, air temperature 20°C
4
= sound power conforming to ISO 3741 and ISO 3742
5
= Sound pressure level measured at a distance of 1 m with a
directivity factor of 4
NOTES CAW WITH 4 PIPES:
1
= water temperature 7/12°C, air temperature dry bulb 27°C, wet bulb
19°C
3
= Water temperature 70 - 60°C; air temperature 20°C
4
= sound power conforming to ISO 3741 and ISO 3742
5
= Sound pressure level measured at a distance of 1 m with a direc-
tivity factor of 4
Ratings and technical data of CAW fan coil units with 2 heat exchangers
Model
3P4
4P4
5P4
6P4
Speed
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
Total cooling capacity (1)
kW
1,03 1,72 1,88 2,05 1,52 2,88 3,28 3,76 2,60 3,90 4,50 4,97 4,25 5,10 5,60 6,20
Sensible cooling capacity (1)
kW
0,81 1,51 1,66 1,82 1,07 2,27 2,60 3,00 1,85 2,90 3,36 3,75 3,15 3,73 4,02 4,45
Water fl ow (1)
l/h
177
295
323
351
295
494
563
645
445
678
781
863
735
890
970 1.075
Pressure drop (1)
kPa
3
8
9
11
8
11
13
17
15
25
32
37
13
19
22
28
Heating capacity (3)
kW
1,1
1,78 1,95
2,2
1,48 2,87 3,14 3,76 2,55 3,86 4,43 4,92 4,80 5,58 6,20 6,80
Water fl ow (3)
l/h
96
155
169
191
129
249
273
327
218
330
380
422
410
477
531
580
Pressure drop (3)
kPa
11
25
29
36
7
22
26
36
12
25
35
41
28
37
42
50
Water content
dm3
0,43
0,86
0,99
1,47
Air fl ow
m3/h
180
400
460
520
200
530
630
750
370
630
760
880
850 1.060 1.160 1.300
Power input
W
5
12
14
17
8
24
28
36
12
34
40
46
13
20
25
41
Sound power level (4)
dB/A
30
41
44
46
32
48
51
55
41
53
57
61
43
48
49
51
Sound pressure level (5)
dB/A
25
36
39
41
27
43
46
50
36
48
52
56
38
43
44
46
Cooling heat exchanger water connections
inches
1 / 2
1 / 2
3 / 4
3 / 4
Heating heat exchanger water connections
inches
1 / 2
1 / 2
1 / 2
3 / 4
Unit dimensions H x L x P
mm
273 x 575 x 575
273 x 575 x 575
273 x 575 x 575
273 x 776 x 776
Grille dimensions H x L x P
mm
64 x 730 x 730
64 x 730 x 730
64 x 730 x 730
64 x 860 x 860
3742551181-I-TEC-CAW-GB.indd 2
3742551181-I-TEC-CAW-GB.indd 2
27/01/2015 13:55:25
27/01/2015 13:55:25