GB
10
4.4.3 - Power supply
• 230V / 1 + Earth / 50Hz power supply from a power supply and protection device (not included) in accordance
with the rules in force. The protection must be ensured by a
two-pole circuit breaker
(not supplied).
Note:
The unit is designed to be connected to a power supply having a TT neutral regime (neutral to ground) or
TN.S regime (to neutral) as per NF C 15-100.
For a IT neutral point connection (isolated neutral), provide ground fault protection.
• The acceptable voltage variation is ± 10% during operation.
• Wire sizes are given for informational purposes only. Wire sizes must be checked and adapted, as required,
according to the installation conditions and with regard to current standards.
Models
Max. current consumption (A)
Section (mm
2
)
CAW 3
0,25
1,5
CAW 4-5
0,40
1,5
Models
Max. current consumption (A)
Section (mm
2
)
CAW 6-8
0.65
1.5
CAW 10
0.95
1.5
4.5 -
ELECTRIC WIRING DIAGRAMS
CAW 3-4-5
3742551181-I-TEC-CAW-GB.indd 10
3742551181-I-TEC-CAW-GB.indd 10
27/01/2015 13:55:35
27/01/2015 13:55:35