52
7-8. Outdoor Fan Speed Control (Cooling and Dry Operation)
●
To optimize performance of the air conditioner, the outdoor fan speed is switched automatically according to the
outdoor temperature.
●
If the outdoor air temperature falls below B°C, the fan speed switches to LOW.
●
If the outdoor air temperature rises above A°C, the fan speed switches to HIGH.
●
This function does not become active in heating operation.
The operating temperature shown as A and B in the chart differ by models.
H
H
L
A
B
Outdoor air
temperature (°C)
Outdoor fan
speed
NOTE
Models
A
B
GRV180R7TAA
27.0°C
23.5°C
GRV220R7TAA
31.0°C
28.5°C