Outdoor Unit GRV180R7TAA
Negative Phase Relay (47C)
RDR-S400
Rating
AC 415V, 3-phase 50Hz
Contact rating
AC 400V, 1A
Operation
Positive phase: ON
Negative phase: OFF
Relay (PR)
MY2-TSDF
Coil rating
DC 24V
Coil resistance
Ω
(at 20°C)
650 ± 10%
Contact rating
AC 200V, 5A
4-way Valve (SC)
LB64012 (Coil), V26-110B (Valve)
Coil rating
AC 220/240V, 50Hz, 6W
Coil resistance
Ω
(at 20°C)
1,740 ± 7%
Electro Magnetic Contactor (MG)
HOE-10TB TH-5A
Magnetic contactor
Coil rating
AC 220–240V, 50Hz / AC 240–260V, 60Hz
Coil resistance
Ω
(at 25°C)
1,260 ± 10%
Contact rating (Main)
AC 440V, 8A
Thermal relay (Overcurrent relay)
Operating amperes
5A
Thermostat (Defrost thermo. 23D)
TRS02-12MSR
Operating temp.
°C
ON
12 ± 2
Diff.
8 deg. below
14
Thermostat (Fan Speed Control 23S)
MQT5S-27YZJ
Switching temp.
°C
high
→
LOW
23.5°C ± 1.5
low
→
HIGH
27.0°C +0
–3
Contact rating
AC 220V, 3A