37
Indoor Unit MCAV220R5VAA
Outdoor Unit GRV220R7TAA
COOLING
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at 230V 50Hz 400V - 3N - 50Hz
Rating Conditions Running Amps. A 0.40 0.55 3.85 4.8
Power Input kW 0.078 0.120 2.552 2.750
Full Load Conditions Running Amps. A 0.40 0.55 4.45 5.4
Power Input kW 0.078 0.120 3.102 3.300
Rating Conditions
: Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
HEATING
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at 230V 50Hz 400 - 3N - 50Hz
Rating Conditions Running Amps. A 0.40 0.55 4.05 5.0
Power Input kW 0.078 0.120 2.802 3.000
Full Load Conditions Running Amps. A 0.40 0.55 4.65 5.6
Power Input kW 0.078 0.120 3.460 3.660
Rating Conditions
: Indoor Air Temperature 20°C D.B.
Outdoor Air Temperature 7°C D.B. / 6°C W.B.
Full Load Conditions : Indoor Air Temperature 27°C D.B.
Outdoor Air Temperature 24°CD.B. / 18°CW.B.