NOTE
If more wires must be spliced than allowed by Table 2, use piggyback crimps as shown in Figure 2.
Figure 2: Piggyback crimp
1
Aluminum wire
2
Copper wire
3
To fixture
4
To box
2. Ensure that each wire extends a minimum of 25.4 mm [1 in.] from any electrical box or wall surface
3. Strip each wire to the length indicated in Figure 3. Do
not
nick or cut the conductors. If a conductor is
damaged, cut the wire and strip it again.
Figure 3: Stripping wires (not to scale)
1
Minimum wire length 25.4 [1.0]
2
Strip length 19.05 [0.75]