23
Lock the keypad during
: Set the number of seconds to lock the keypad if Keypad lock option is set.
Maximum value 255, Minimum value 1.
Reader type
: Set the Wiegand output type. Additional options are available depending of the
Wiegand option selected e.g. Site code management. Set Wiegand 26 bit for TDSi readers.
Below is a typical setup for TDSi readers with keypad.
Clock & Data
It is possible to set the number of characters when setting the reader to Clock & Data. Maximum value
13. Minimum value 1. This will take the least significant digit (LSD). For example if an output was set to 8
digits and the following was reported: 85476456. If the output was then set to 4, the number taken by
the unit would be 6456.
Custom Wiegand
Select Custom Wiegand from the dropdown menu.
Auto detection of the Wiegand format is provided. Ensure the required reader is attached to the
reader channel. Enter the card number in the
Credential
data field. Click
Start
and present the card
to the reader. The Received frame data field will display the Wiegand data received by the unit.
Click
Save
to program the Wiegand format to the controller.
Summary of Contents for GARDiS Series
Page 1: ...GARDiS Controller Embedded Web Server User Manual UM0121 Issue 3...
Page 4: ...Timed Anti passback 46 Troubleshooting 47 Restoring from backup 47...
Page 14: ...14 Step 14 Enter details for the new user i e last name...
Page 25: ...25...
Page 30: ...30 This will set the selected schedule within the dropdown...
Page 34: ...34 Step 1 Step 2 Step 3 Step 4...