SWS 

600L, 1000L

  Input Voltage Range

Input voltage range is single phase 85

 - 

265VAC (47 - 63Hz) or 

120 - 350VDC. Input voltage, which is out of specifi cation, may 

cause unit damage. Rated input voltage for safety standard 

application is 100AC-240VAC (50/60Hz).

  Output Voltage Range

Output voltage is set to the rated value at shipment. V.ADJ trim-

mer on the front panel side can be used to adjust the output 

voltage within the range specifi ed  (refer  to  specifi cations  for 

adjustable range). 

To turn the trimmer clockwise, the output voltage will be in-

creased.  Take  note  when  the  output  voltage  is  increased  ex-

cessively, over voltage protection (OVP) function may trigger 

and output voltage will be shut down.

  Over Voltage Protection (OVP)

The OVP function (inverter shutdown method, manual re-

set type) is provided. OVP function operates within 

specifi ed 

range (refer to specifi cation)

 of the rated output voltage value 

and  the  output  will  be  shut  down  when  OVP  function  triggers 

(refer to specifi cations for OVP range of each models).  To reset 

OVP, remove the input of power supply for a few minutes, and 

then re-input. Or, use CNT to reset (remote ON/OFF : OFF to 

ON). OVP value is fi xed and not to be adjusted externally. Never 

apply more than rated output voltage to output terminal, which 

may lead to damage. In the case of inductive load, use decou-

pling diode at output line.

  Over Current Protection (OCP)

The OCP function is provided. OCP characteristic is constant 

current limiting, automatic recovery. OCP function operates 

when the output current exceeds 105% (24V output model: 

101%  of  peak  current)  of  maximum  DC  output  current  speci-

fi cation. The output will be automatically recovered when the 

overload condition is cancelled. Never operate the unit under 

over current or shorted conditions for more than 30 seconds, 

which may lead to damage. OCP setting is fi xed and not to be 

adjusted externally.

  Over Temperature Protection (OTP)

The OTP function (manual reset type) is provided. When ambi-

ent or internal temperature rises abnormally, OTP function op-

erates and output will be shut down. After shut down, remove 

the input and cool it down to reset OTP. Then  re-input.

  Power Failure Detection Circuit (ALM)

Power failure detection circuit is provided. ALM (Alarm) signal 

will turn“High”level to indicate the abnormal status when con-

verter stops. Please take note in parallel or N+1 operation at light 

load condition, maybe only one of the power supply operates 

and other power supply stops. When the built-in FAN motor of 

this power supply unit stops, ALM signal will turn to “High” too. 

If the output voltage is decreased to less than 20% of rated 

voltage, or decreased rapidly through an external adjustment 

mechanism when load is light, the ALM signal may turn “High”. 

The ALM signal is isolated from input and output by a photo-

mosfet. It uses the open collector method shown as below.

  Remote Sensing (+S, -S terminal)

This function compensates voltage drop of wiring from output 

terminals to load terminals. Connect “+S” terminal to “+” termi-

nal of load and “-S” terminal to “-” terminal of load with sensing 

wires. The total line voltage drop (+ side line and - side line) shall 

be less than 0.3V. In case that sensing lines are too long, it is 

necessary to put an electrolytic capacitor in following places.

 (1) across the load terminal,

 (2) between “+S” terminal and “+V” terminal,

 (3) between “-S” terminal and “-V” terminal.

When the function of remote sensing is not used, cS 

terminal to +Vm terminal, and -S terminal to -Vm terminal by the 

attachment connector.

If remote sensing terminals are opened, the stability and the 

accuracy of the output deteriorated. Therefore, terminal  +S, -S 

must be connected.

  Remote ON/OFF Control

Remote ON/OFF control is provided. 

Using this function, output on/off is allowed to control without 

input voltage on/off. 

 (1) The maximum input voltage to CNT2 terminal is 12V, and the 

maximum allowable reverse voltage is -1V; Current fl ow into 

CNT2 is 5mA typical and 12mA maximum.

 (2) A switch and relay or a transistor can be used as ON/OFF switch.

 (3) Remote ON/OFF control circuit is isolated from the input 

and output by a photo-coupler and can be controlled re-

gardless of the output potential (+ or -). Connect TOG termi-

nal to ground of control signal.

Specifications of remote ON/OFF

CNT2-TOG current or voltage condition:

Connection method

(a)

(b)

 (c)

SW Logic

Output on

SW open

(0.1mA max)

SW open

(0.1mA max)

SW close

(0.5V max)

Output off

SW close

(3mA min)

SW close

(3mA min)

SW open

(0.1mA max)

Pin

CNT2, TOG

CNT1, CNT2, TOG, G2 CNT1, CNT2, TOG, G2

Imax=10mA

ALM

1

Vmax=50V

+

CN1

+Vm

+S

-S

-Vm

-V

+V

Load

+

-

+

4. Functions and Precautions

Summary of Contents for SWS-L Series

Page 1: ...SWS L Series Compact and high power AC DC power supply...

Page 2: ...All specifications are subject to change without notice...

Page 3: ...Lambda always provides our customers with the best power solutions by combining extensive industry market research with our advanced R D expertise ensuring that our power supplies will continue to evo...

Page 4: ...lation Withstand Voltage Input Output 3 0kVAC 20mA Input FG 2 0kVAC 20mA Output FG 500VAC 100mA 60V model 651VAC 130mA Output CNT ALM AUX 100VAC 100mA for 1min Isolation Resistance Input FG Input Outp...

Page 5: ...VOLTAGE RANGE NOMINAL OUTPUT VOLTAGE NOMINAL OUTPUT CURRENT AND PEAK OUTPUT CURRENT ARE SHOWN ON THE NAME PLATE IN ACCORDANCE WITH THE SPECIFICATIONS 2 COUNTRY OF MANUFACTURE IS SHOWN ON THE NAME PLA...

Page 6: ...Ta 25 C first inrush second inrush Leakage Current typ 11 mA 0 1mA at 115VAC 60Hz 0 2mA at 230VAC 60Hz Output Nominal Voltage VDC 3 3 5 12 15 24 36 48 60 Maximum Current Peak Current 1 A 200 88 70 44...

Page 7: ...2 5 37 MAX 29 AIR FLOW 165 0 5 240 1 3 MAX BOTTOM SIDE SEE NOTE C 150 1 110 0 5 20 FG FG L N 38 0 5 4 M4 2 9 10 10 20 2 1 23 1 17 9 29 165 0 5 BOTH SIDES SEE NOTE C 61 1 11 5 CN2 CN3 LED CN1 AMBDA L A...

Page 8: ...ARY G1 COM COM COM CNT2 TOG NC PV S ALM PC S Vm Vm V V OUTPUT ALARM FAN PFC CIRCUIT RECTIFIER LINE FILTER Sequence Time Chart SWS1000L INPUT VOLTAGE RANGE 85 265VAC FUSE RATING 20A PFC FREQUENCY 130kH...

Page 9: ...azardous voltage These terminals must not be user and service person accessible This power supply is capable of providing hazardous energy output 240VA the end equipment manuafacturer must provide pro...

Page 10: ...and function They are connected to each other in this power supply unit When the pin of CN1 side is shorted the same function pins of CN2 side are also shorted Please note that the function cannot be...

Page 11: ...load line Output current of each terminal screw shall be 60A or less for SWS600L Panel Side Basic connection Local sensing Connect S terminal to Vm terminal and S terminal to Vm terminal SWS600L SWS10...

Page 12: ...ure Detection Circuit ALM Power failure detection circuit is provided ALM Alarm signal will turn High level to indicate the abnormal status when con verter stops Please take note in parallel or N 1 op...

Page 13: ...hort as possible and same length and twisted 1 Adjust the output voltage of each power supply to be same value within 1 or 100mV whichever is smaller 2 Use same length and type of wires for all load l...

Page 14: ...each for 1 minute When testing withstand voltage set current limit of withstand voltage test equipment at 20mA Output chassis and Output Control 100mA The applied voltage must be gradually increased f...

Page 15: ...ut Peak Current For 24V 48V output model please meet the following condi tions Reduce peak current value according to output derating as section 4 2 Input voltage range AC170V 265V Continuous Peak out...

Page 16: ...This power supply has ventilating holes on the front and back side panels Keep these two areas freely as much as possible 2 The maximum allowable penetration for screw is 6mm Incomplete thread of moun...

Page 17: ...m Type Size Conductor part Insulation part UL1007 AWG 28 1 2 0 55 0 60 1 6 UL1007 AWG 26 1 3 0 60 0 65 1 7 UL1007 AWG 24 1 5 0 62 0 67 1 8 Note1 Crimp height at wire barrel should be set to pre determ...

Page 18: ...ent temperature 9 Special instructions for IEC EN UL CSA 60601 1 SWS1000L only 1 These products are designed for continuous operation within an overall enclosure and must be mounted such that access t...

Page 19: ...f use function of the Remote ON OFF control check if the Remote ON OFF control is properly used 7 Check if the built in FAN is not stopped Is FAN stopped by something irregular or etc If FAN stops the...

Page 20: ...Each Manufacturing Company This datasheet has been downloaded from www EEworld com cn Free Download Daily Updated Database 100 Free Datasheet Search Site 100 Free IC Replacement Search Site Convenien...

Reviews: