Page 13 of 29 

 

 

 

17027 issue 23, June 2014 

 

 

 

 

 

 

 

 

 

    

    

 

Alpha 1000 Handbook

 

Special Instructions for medical applications (IEC 60601-1:1988 + A1:1991 + A2:1995; EN 60601-1: 1990 + 
A1:1993 + A2:1995; UL 60601-1, 1st Edition, 2006-04-26 (includes National Differences for USA) CAN/CSA-
C22.2 No. 601.1-M90 (R2005) (includes National Differences for Canada); IEC 60601-1:2005; EN 60601-1:2006; 
ANSI/AAMI ES 60601-1:2005; CSA 22.2 No 60601-1:2008)  -   Applicable to products with L, R and T Input 
Filter Options only 

 
These products are designed for continuous operation within an overall enclosure, and must be mounted such that 
access to the mains terminals is restricted.  
 
These products are NOT suitable for use in the presence of flammable anaesthetic mixtures with air or with oxygen, 
or with nitrous oxide. 
 
For IEC60601-1, EN60601-1 and UL/CSA 60601-1 (Second Edition standards), the Alpha 1000 range provides 
Basic insulation between input and outputs, and functional insulation between outputs and earth. 
 
For IEC 60601-1:2005; EN 60601-1:2006; ANSI/AAMI ES 60601-1:2005; CSA 22.2 No 60601-1:2008), the Alpha 
1000 range provides reinforced insulation between input and outputs (2 MOOPs) for all products. Between outputs 
and earth there is functional insulation only. 

 

Connect only apparatus complying with the standards listed above as appropriate to the signal ports. 

These products are classed as ordinary equipment and are not protected against the ingress of water (IPX0). 

Reference should be made to local regulations concerning the disposal of these products at the end of their useful 
life. 

Where any part of this product is made accessible to the operator in the end use equipment, the operator must not 
touch this part and the patient at the same time. 

These products have not been assessed to IEC/EN60601-1-2 (EMC) but EMC test data is available from TDK-
Lambda UK Ltd. 

WARNING: No modification of this product is allowed. 

Except for permanently installed equipment, the overall equipment into which these products are installed must have 
double pole fusing on the input mains supply. The products themselves have single pole fusing in the live line only. 

 
Environmental Specifications:  
 

Description 

Operation 

Storage 

Use 

Indoor 

Temperature 

0 to 50°C (derating 2.5%°C above 50°C to 65°C -

Not covered by approvals). 

-40°C to +70°C 

Humidity 

5 to 95% RH non-condensing 

5% to 95% RH non-

condensing 

Altitude 

-200m to 3000m 

-200m to 5000m. 

Pressure 

70kPa to 106kPa 

54kPa to 106kPa 

Orientation 

Horizontal with chassis lowest, on either side or 

vertical with the airflow upwards. 

All 

Material Group 

IIIb 

Pollution Degree 

Overvoltage Category 

II 

Class 

Weight 

3 kg (Dependent on configuration) 

IP Rating 

IPX0 

 

 

Level of Insulation:   

Dielectric Strength testing is carried out as follows: 
Primary mains circuit to earth - 2.25 - 2.35kVDC 
Primary mains circuits to transformer core - 4.25 - 4.35kVDC* 
Primary mains circuits to secondary -4.25 - 4.35kVDC.*

 

Outputs to each other and to earth are isolated to 500VDC. 
*This test is not possible with modules fitted to the unit as damage to RFI capacitors will occur) 
 

Summary of Contents for Alpha 1000

Page 1: ...el except as stated in the product limitations in this handbook Input Parameters This product must be operated within the input parameters stated in the product limitations in this handbook End of Lif...

Page 2: ...tent contact with these module output terminals If set such that hazardous energy can occur then the module terminals or connections must not be user accessible HOT SURFACE External Hot Surfaces In ac...

Page 3: ...in den Produktgrenzen dieses Handbuches ausgezeichnet ist Eingangsparameter Dieses Produkt muss innerhalb der Eingangsparameter die in den Produktgrenzen dieses Handbuches angegeben sind betrieben we...

Page 4: ...r Servicepersonal vor unbeabsichtigtem Kontakt mit den Ausgangsanschl ssen dieser Module vorsehen Kann aufgrund der Einstellung gef hrliche elektrische Energie auftreten d rfen die Modulanschl sse f r...

Page 5: ...l intensit nominale marqu e sur la plaque signal tique sauf indications contraires dans les limitations du produit d crit dans ce manuel Param tres d entr e Ce produit doit tre utilis l int rieur des...

Page 6: ...ension de sortie Le fabricant de l quipement final doit assurer la protection des techniciens d entretien contre un contact involontaire avec les bornes de sortie de ces modules Si une telle tension d...

Page 7: ...vratensione II Questo prodotto contiene schede di circuiti stampati in materiali di Gruppo IIIb Carico in uscita La potenza in uscita ottenuta dall alimentatore non deve superare la potenza nominale i...

Page 8: ...rogare energia pericolosa 240 VA a seconda della tensione in uscita impostata I produttori delle apparecchiature finali sono tenuti a proteggere il personale di manutenzione dal rischio di contatto ac...

Page 9: ...utilizan policloruros de bifenilo del Grupo de materiales IIIb Carga de salida La potencia de salida tomada de la fuente de alimentaci n no puede sobrepasar el valor nominal indicado en la etiqueta de...

Page 10: ...eden generar energ a peligrosa 240VA dependiendo de la configuraci n de la tensi n de salida Los fabricantes de equipos finales deben proteger al personal de servicio contra un contacto accidental con...

Page 11: ...retens o II S o utilizadas placas de circuitos impressos do grupo de materiais IIIb Carga de sa da A pot ncia de sa da extra da da fonte de alimenta o n o deve exceder a classifica o assinalada na eti...

Page 12: ...energia perigosa 240 VA de acordo com a configura o da tens o de sa da O equipamento final do fabricante deve garantir que o pessoal de assist ncia est protegido contra contactos inadvertidos com est...

Page 13: ...water IPX0 Reference should be made to local regulations concerning the disposal of these products at the end of their useful life Where any part of this product is made accessible to the operator in...

Page 14: ...uration Code Alpha 1000 and CA1000 are identical Alpha 1000 or CA1000 may be followed by TL RL LL or ML Where TL Tiny leakage input filter RL Reduced leakage input filter LL Low leakage input filter M...

Page 15: ...ules providing a max output of up to 16V only or b Identical to _PA except that the module is paralleled at the output of the module with busbar linking _IN Provides an external signal which may be us...

Page 16: ...vertical with airflow downwards Model CA1250 12C_MF 12FF 12FF 12FF NS AMD 005 Input voltage range 207 264Vac Outputs C Module 13V max 16A max F Module 13V max 30A max F Module 13V max 30A max F Modul...

Page 17: ...ing for Hazardous Energy A 4 5 5 5V 60A 2 1 60 79 2A 3V AA 4 5 6 2V 60A 2 1 60 79 2A 3V B 4 5 5 5V 25A 1 1 25 33A BB 4 5 6 5V 25A 1 1 25 33A C 5 16V 16A 1 2 32 21 2A 11 3V D 18 29V 8A 1 4 32 10 6A 22...

Page 18: ...les can be used up to 5A on the 18 29V channel in slots 1 to 6 and up to 3A in slot 7 P modules can be used up to 8A in the 5 16V channel in slots 1 to 6 and up to 5A in slot 7 Q modules can be used u...

Page 19: ...be used to ensure the PSU is operated within its ratings 1 Calculate the output power for each module Volts x Amps 2 Total power for slots 1 3 must be 720W Total power for slots 4 7 must be 600W Total...

Page 20: ...Page 20 of 29 17027 issue 23 June 2014 Alpha 1000 Handbook Main Base PCB...

Page 21: ...Page 21 of 29 17027 issue 23 June 2014 Alpha 1000 Handbook Forward Converter No 1 Forward Converter No 2...

Page 22: ...Page 22 of 29 17027 issue 23 June 2014 Alpha 1000 Handbook Single Module PCB Dual Module PCB...

Page 23: ...Page 23 of 29 17027 issue 23 June 2014 Alpha 1000 Handbook Twin Module PCB J Module PCB...

Page 24: ...Page 24 of 29 17027 issue 23 June 2014 Alpha 1000 Handbook L Module PCB S Module PCB...

Page 25: ...Page 25 of 29 17027 issue 23 June 2014 Alpha 1000 Handbook T Module PCB MF Option MFV Option...

Page 26: ...Page 26 of 29 17027 issue 23 June 2014 Alpha 1000 Handbook...

Page 27: ...n PP Parrallel Connector Six way Molex 90142 0006 Crimp terminals 90119 2109 MF MFL MFE MFU MFV Pin 1 Inhibit Low Enable Low Inhibit Low Inhibit Low Pin 2 5V Aux 5V Aux 5V Aux 5V Aux Pin 3 Power Fail...

Page 28: ...119 2109 Crimp terminals 90119 2109 1 ve sense 2 Module Good 3 Star Point 4 ve sense 5 ve power 6 Star Point Option RP Remote Programming Module Positions 1 Not connected 2 Module Good 3 Inhibit input...

Page 29: ...Alpha 1000 Handbook Customer fixings TDK Lambda UK Ltd Kingsley Avenue Ilfracombe Devon EX34 8ES Telephone Sales and Service 44 0 1271 856666 Head Of ce and Works 44 0 1271 856600 Facsimile 44 0 1271...

Reviews: